ESIE15-13B
Field Setting from Outdoor Unit PCB
Field Setting
85
Setting of Demand 2 operation
With this setting, compressor operation can be controlled to reduce power consumption.
(60% - 80% demand is available when a demand adapter (optional accessory) is used.)
[Work procedure]
Setting item
Setting condition
Description
Demand 2 operation
30% demand
Operates with 30% of rated
power consumption.
40% demand (factory setting) Operates with 40% of rated
power consumption.
50% demand
Operates with 50% of rated
power consumption.
h
: OFF
l
: BLINK
k
: ON
Operating procedure
H1P H2P H3P H4P H5P H6P H7P
Push and hold the MODE (BS1) button of "Setting mode 1" for 5 seconds
or more and set to "Setting mode 2."
k h h h h h h
Push the SET (BS2) button three times to set the LED display as shown
in the table on the right.
k h h h h k k
Push the RETURN (BS3) button once. (Present settings are displayed.)
k h h h h l h
Push the SET (BS2) button to set the LED
display as shown in the table on the right.
30% of rated power consumption
k h h h l h h
40% of rated power consumption
k h h h h l h
50% of rated power consumption
k h h h h h l
Push the RETURN (BS3) button once to make a
decision.
30% of rated power consumption
k h h h k h h
40% of rated power consumption
k h h h h k h
50% of rated power consumption
k h h h h h k
Push the RETURN (BS3) button once again for execution. (The LED
display is in the initial status of "Setting mode 2".)
k h h h h h h
Push the MODE (BS1) button once to return to Setting mode 1 (normal
operation).
h h h h h h h
Summary of Contents for GQI-Eco Series
Page 2: ......
Page 6: ...ESIE15 13B iv Table of Contents...
Page 14: ...Introduction ESIE15 13B xii...
Page 18: ...Outlook Outdoor Units ESIE15 13B 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13B 8 General Information...
Page 108: ...Emergency Operation ESIE15 13B 94 Field Setting...