ESIE15-13B
Field Setting from Remote Controller
Field Setting
71
Automatic Operation Mode Control
When selecting “Automatic Operation Mode” with the remote controller, conducts the most
comfortable operation in which you do not feel too cool or too hot.
Automatic Restart after Power Failure Reset
For the air conditioners with no setting for the function, the units will be left in the stop condition
when the power supply is reset automatically after power failure reset or the main power supply
is turned on again after once turned off. However, for the air conditioners with the setting (same
as factory setting), the units may start automatically after power failure reset or the main power
supply turned on again (return to the same operation condition as that of before power failure).
For the above reasons, when the unit is set enabling to utilize “Auto restart function after power
failure reset”, utmost care should be paid for the occurrence of the following situation.
Setting of Normal Airflow
Make the following setting according to the ceiling height. The setting position No. is set to “01”
at the factory.
FCQG71
FCQG100-140
FHQG71
FHQG100-140
Outdoor air temperature
Indoor air temperature
Temperature set by remote controller
Calculates and controls the optimum indoor
temperature
Caution 1. The air conditioner starts operation suddenly after power failure reset or
the main power supply turned on again. Consequently, the user might be
surprised (with question for the reason why).
2. In the service work, for example, turning off the main power switch during
the unit is in operation, and turning on the switch again after the work is
completed start the unit operation (the fan rotates).
Mode No.
First code No.
Second code No.
Ceiling height (m)
13 (23)
0
01
≤
2.7
02
2.7 - 3.0
03
3.0 - 3.5
Mode No.
First code No.
Second code No.
Ceiling height (m)
13 (23)
0
01
≤
3.2
02
3.2 - 3.6
03
3.6 - 4.2
Mode No.
First code No.
Second code No.
Ceiling height (m)
13(23)
0
01
≤
2.7
02
2.7 - 3.5
Mode No.
First code No.
Second code No.
Ceiling height (m)
13(23)
0
01
≤
3.8
02
3.8 - 4.3
Summary of Contents for GQI-Eco Series
Page 2: ......
Page 6: ...ESIE15 13B iv Table of Contents...
Page 14: ...Introduction ESIE15 13B xii...
Page 18: ...Outlook Outdoor Units ESIE15 13B 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13B 8 General Information...
Page 108: ...Emergency Operation ESIE15 13B 94 Field Setting...