ESIE15-13B
Troubleshooting by Remote Controller
Service Diagnosis
171
4.33 Power Supply Voltage Abnormality
Remote
Controller
Display
U2
Applicable
Models
RZQG
Method of Error
Detection
The error is detected according to the voltage of main circuit capacitor built in the inverter and
power supply voltage.
Error Decision
Conditions
When the voltage of main circuit capacitor built in the inverter and power supply voltage drop or
when the power failure of several tens of ms or more is generated.
Supposed
Causes
Drop in power supply voltage
Defective outdoor fan motor
Instantaneous power failure
Defective outdoor unit inverter PCB
Main circuit parts damaged