Field Setting from Remote Controller
ESIE15-13B
78
Field Setting
Graph 1
Target evaporating temperature control in case of factory setting 16(26)-2-01:
Te target acceptable area
Remote controller setting temp.
Te target limited
≤
20˚C
(to protect the comp.)
Te target limited
≤
Indoor temp. – 11˚
(not to rising wetbulb)
Te (see note) target
acceptable area
Indoor temp.
>
setting
→
Te target down
Indoor temp.
<
setting
→
Te target up
Te target limited
≥
Indoor temp. – 25˚
(not to sweat)
Te target limited
≥
2˚C
(not to freeze)
Freeze protection
(40 min. integrated coil temp.
≤
-1˚C)
Indoor Temp
(˚C DB)
Summary of Contents for GQI-Eco Series
Page 2: ......
Page 6: ...ESIE15 13B iv Table of Contents...
Page 14: ...Introduction ESIE15 13B xii...
Page 18: ...Outlook Outdoor Units ESIE15 13B 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13B 8 General Information...
Page 108: ...Emergency Operation ESIE15 13B 94 Field Setting...