Field Setting from Remote Controller
ESIE15-13B
68
Field Setting
Note:
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses. (Even if the
setting are made for the entire group, the display always indicates "01".)
*2. For FHQG, the second code No. of the "Airflow range setting is set at "03".
3. "88" may be displayed to indicate the remote controller is resetting when returning to the
normal mode.
4. This function does not work when "SET BACK Function" is set by remote controller.
5. This is the case when the remote sensor (optional kit) is used.
6. This is the case when the sensor option (optional kit) is used.
7. Wind block: one of 4 flaps can be set a block position. (block position = closed position)
Wind can not be blocked 100% but mostly blocked without additional parts.
2.3.1 Detailed Explanation of Setting Modes
Filter Cleaning Sign Interval
When "Display" is selected in "Filter cleaning sign" after the unit runs for certain time, "Filter
cleaning" will be displayed on the remote controller. This setting is used when the display
interval of "Filter cleaning" needs to be changed on occasions such as when the filter has been
heavily contaminated.
Remote Controller Thermistor
Select the thermistor to control room temperature.
The factory setting for the Second Code No. is "02" and room temperature is controlled by the
indoor unit suction air thermistor.
When the Second Code No. is set to "01", room temperature is controlled by the indoor unit
suction air thermistor and the room temperature thermistor in remote controller as following
figures.
14
(24)
2
The largest time interval
for Dust Collection Sign
Display for "self
cleaning decoration
panel"
About 1250 hrs
(Dusty place)
About 2500 hrs
About 5000 hrs
(less dusty
place)
—
—
4
Display or non-display
of green lamp on the
selfcleaning decoration
panel
Display both: -
airconditioning
operation, -filter
auto cleaning
Non display: -
airconditioning
operation,
Display: -filter auto
cleaning
Display: -
airconditioning
operation, Non
display: -filter
auto cleaning
—
—
8
Auto control operation
for Filter Auto Cleaning
Auto control
operation
Not auto control
operation
—
—
—
9
Filter cleaning time for
"selfcleaningdecoration
panel"
Normal place in
terms of dust
(Normal office)
In case of dusty
place
—
—
—
15
(25)
5
Individual setting of
ventilation
Normal
Individual
operation
—
—
—
1b
(2b)
14
Wind block (note 7)
enable / disable setting Enable
—
—
—
disable
Mode No. First Code
No.
Second
Code No.
Long Life Filter
Setting
10 (20)
0
01
2,500 hrs.
Contamination Light
02
1,250 hrs.
Contamination Heavy
Mode No.
First Code
No.
Second
Code No.
Thermistor that controls room temperature
10 (20)
2
01
Room temperature thermistor in remote controller and
indoor unit suction air thermistor
02
Indoor unit suction thermistor
Summary of Contents for GQI-Eco Series
Page 2: ......
Page 6: ...ESIE15 13B iv Table of Contents...
Page 14: ...Introduction ESIE15 13B xii...
Page 18: ...Outlook Outdoor Units ESIE15 13B 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13B 8 General Information...
Page 108: ...Emergency Operation ESIE15 13B 94 Field Setting...