14.1
Data for designing the flue gas pipe
Device
Burner
load in kW
Rated output in kW
Flue gas mass flow in g/s
Flue gas temperature in
°C
Available pump-
ing pressure in
Pa
50/30 °C
80/60 °C
Natural gas
E/H
Natural gas
LL/L
Liquefied
petroleum
gas
50/30 °C
80/60 °C
GCU compact
315/515 (Biv)
3.0
3.2
2.9
1.32
1.27
1.28
31
61
40
15.0
15.7
14.6
6.45
6.18
6.26
44
63
170
GCU compact
320/520 (Biv)
3.0
3.2
2.9
1.32
1.27
1.28
31
61
40
20.0
20.9
19.5
8.59
8.24
8.34
49
69
200
GCU compact
524 (Biv)
4.0/5.0
(G31)
4.3/5.4
(G31)
3.9/4.9
(G31)
1.76
1.69
2.14
31
61
40
24.0
25.0
23.4
10.21
9.80
9.92
46
64
185
GCU compact
528 (Biv)
4.0/5.0
(G31)
4.3/5.4
(G31)
3.9/4.9
(G31)
1.76
1.69
2.14
31
61
40
28.0
29.1
27.2
11.73
11.25
11.39
50
68
200
Tab. 14-1
Triple values for chimney design,
(G31)
= liquid gas setting (flue gas flow dependent on heat output, see
)
14.2
Emissions measurement
The control measurement can be made by an easily selectable auto-
matic function (see also enclosed "Control system instructions").
1
Press the Exit button for at least 5 secs.
è
The "Special Level" menu is displayed.
2
Use the rotary button to select the "Emissions measurement"
program.
3
Confirm the changes with a brief push of the rotary switch.
è
The following load types are available for selection:
–
Off: The emission measurement is switched off, any heat
generators switched on by the GCU compact control func-
tions continue to be regulated normally.
–
Base load: The heat generator is switched on and operated
at the minimum output of the heat generator, irrespective of
the set operating mode.
–
Full load: The heat generator is switched on and operated at
the maximum output of the heat generator, irrespective of
the set operating mode.
4
Use the rotary button to select the "Full Load" load type,
but do
not confirm
.
è
Display: "Full Load"
è
The burner is turned on for 30 min. and is regulated at max-
imum load.
5
Use the rotary button to select the "Base Load" load type,
but
do not confirm
.
è
Display: "Base Load"
è
The modulating oil burner runs at minimum output for
30 mins.
6
Cancel and jump back by:
–
pushing the exit button or rotary switch again
–
Selection of a different menu using the rotary switch and
confirmation.
Special Level
Emissions measurement
Manual Operation
Emissions measurement
Off
Emissions measurement
Base Load
Emissions measurement
Full Load
Emissions measurement
Full Load
T-HS
T-HS
T-HS
T-HS
Fig. 14-1
Symbolic brief instructions for emission measurement