4
Set-up and installation
Installation and operating instructions
21
Gas Combi Unit
Floor-standing gas condensing boiler with integrated heat storage
008.1543899_02 – 04/2019 – EN
▪ For ambient air-dependent mode, the installation room must be
free from aggressive vapours (e.g. hair spray, perchloroethylene,
carbon tetrachloride), heavy dust formation and high atmospheric
humidity (e.g. laundry).
▪
Outdoor installation
is not permissible.
▪ Installation in an explosion-risk environment is not permissible.
▪ The electronic controller may never be exposed to the effects of
the weather.
▪ The storage tank may
not be exposed to continuous direct
sunlight
, as the UV radiation and the effects of the weather will
damage the plastic.
▪ The GCU compact must be installed
protected from frost
.
Surface temperatures, minimum distance
DANGER: RISK OF BURNING
The plastic wall of the storage tank of the GCU compact
can melt under the effects of external heat (>80 °C) and, in
extreme cases, can catch fire.
▪ Only install the GCU compact with a minimum distance
of 1 m to other heat sources (>80 °C) (e.g. electrical
heater, oil heater, chimney) and the material to be com-
busted.
CAUTION
If the GCU compact is not installed a
sufficient
dis-
tance
below
the flat solar panels (the top edge of the stor-
age tank is higher than the bottom edge of the solar pan-
els), the unpressurised solar system in the outdoor area
will not be able to drain completely.
▪ When a solar connection is used, install the GCU com-
pact low enough at the flat solar panels (observe min-
imum gradient in the solar connection lines).
▪ In ambient air-independent mode with rated power, the design
does not allow temperatures > 70 °C on any component outside
the device panels. Therefore, no minimum distance is specified for
components made of flammable materials.
▪ A minimum distance of 50 mm between the flue gas line and flam-
mable components should be maintained in a partial ambient air-
independent and ambient air-dependent operation (separate flue
gas/air supply pipes).
▪ Do not use or store easily inflammable and easily combustible
substances directly next to the GCU compact (minimum distance
1 m, see
).
▪ When installing the device as described in
, we recom-
mend maintaining the minimum distances from walls and ceilings
in order to perform maintenance and repair work without excess-
ive installation effort.
4.4.2
Installing the device
WARNING
The GCU compact is top-heavy in the unfilled state and
could tip over during transport, which could put persons in
danger or damage the device.
▪ Secure the GCU compact well, transport carefully, use
handles.
Precondition
▪ The installation site complies with applicable country-specific reg-
ulations and meets the minimum requirements described in
.
Installation
1
Remove the packaging and dispose of it in an environment-
friendly manner.
2
Pull the cover screens off the storage tank (
unscrew the threaded fittings (
ings at which the handles are to be fitted.
3
Screw the handles (
, item A) into the now uncovered
threaded holes.
Fig. 4-9
Installing the handles (for legend, see
)
4
Carefully transport the GCU compact to the installation site using
the
handles
.
5
Installing the GCU compact at the installation site.
▪
Recommended minimum distances
:
To the wall:
to the rear (s1/s2): ≥ 200 mm
(5)
to the left (s3): ≥ 300 mm
to the right (s4): ≥ 300 mm
(5)
to the ceiling (s
D
): ≥ 200 mm.
▪ Install
close to the withdrawal point
.
(5)
or the values according to
(depending on the flue gas connection)