5
Commissioning
Installation and operating instructions
39
Gas Combi Unit
Floor-standing gas condensing boiler with integrated heat storage
008.1543899_02 – 04/2019 – EN
6
In the [Emissions measurement] program, choose the [Base
Load] setting (see Emissions measurement),
but do not con-
firm
.
▪ Make sure that heat can dissipate into the heating network dur-
ing emission measurement.
▪ Use the flue gas analyser to check the burner settings and com-
.
▪ If the O
2
/CO
2
concentrations are within the permissible values:
No further measures required.
▪ If the O
2
/CO
2
concentrations are outside the permissible values:
Carry out 100 % calibration and set [Drop Io-base] so that the
setting range is reached (see
) and repeat measure-
ment from step 5.
▪ Document the measured values on the "Installation certificate"
form and in the operating manual.
7
End the program [Emissions measurement].
8
Set manual operation on the RoCon BF controller (see operating
instructions "RoCon BF" controller).
9
Check the resistance in the flue gas pipe (see
Type
GCU compact 315 / 515 (Biv)
Gas type
(test gas)
(10)
Burner load
O
2
content in
%
CO
2
content in
%
Natural gas E/H
(G20)
Base Load
6.5 – 7.2
7.7 – 8.1
Full Load
5.2 – 5.9
8.4 – 8.8
Natural gas LL/
L (G25)
Base Load
5.5 – 6.2
8.1 – 8.5
Full Load
4.4 – 5.1
8.7 – 9.1
Propane
(11)
(G31)
Base Load
6.5 – 6.9
9.2 – 9.5
Full Load
4.5 – 5.3
10.3 – 10.8
Tab. 5-1
Commissioning control values for GCU compact 315
and GCU compact 515 for various gas types
Type
GCU compact 320 / 520 (Biv)
Gas type
(test gas)
(10)
Burner load
O
2
content in
%
CO
2
content in
%
Natural gas E/H
(G20)
Base Load
6.5 – 7.2
7.7 – 8.1
Full Load
5.6 – 6.3
8.2 – 8.6
Natural gas LL/
L (G25)
Base Load
5.5 – 6.2
8.1 – 8.5
Full Load
4.6 – 5.3
8.6 – 9.0
Propane
(11)
(G31)
Base Load
6.5 – 6.9
9.2 – 9.5
Full Load
4.9 – 5.8
10.0 – 10.5
Tab. 5-2
Commissioning control values for GCU compact 320
and GCU compact 520 for various gas types
Type
GCU compact 524 (BIV)
Gas type
(test gas)
(10)
Burner load
O
2
content in
%
CO
2
content in
%
Natural gas E/H
(G20)
Base Load
5.6 – 6.1
8.3 – 8.6
Full Load
5.6 – 6.1
8.3 – 8.6
Natural gas LL/
L (G25)
Base Load
5.1 – 5.7
8.4 – 8.7
Full Load
4.7 – 5.3
8.6 – 8.9
Propane
(11)
(G31)
Base Load
5.1 – 5.7
10.0 – 10.4
Full Load
4.7 – 5.4
10.2 – 10.7
Tab. 5-3
Commissioning control values for GCU compact 524 for
various gas types
Type
GCU compact 528 (BIV)
Gas type
(test gas)
(10)
Burner load
O
2
content in
%
CO
2
content in
%
Natural gas E/H
(G20)
Base Load
5.6 – 6.1
8.3 – 8.6
Full Load
5.1 – 5.8
8.5 – 8.9
Natural gas LL/
L (G25)
Base Load
5.1 – 5.7
8.4 – 8.7
Full Load
4.7 – 5.3
8.6 – 8.9
Propane
(11)
(G31)
Base Load
5.1 – 5.7
10.0 – 10.4
Full Load
4.7 – 5.4
10.2 – 10.7
Tab. 5-4
Commissioning control values for GCU compact 528 for
various gas types
5.1.4
After commissioning
1
Install the protective cover (see
2
Check all items of the "Checklist after commissioning" (see
3
Log the test results on the checklist.
Only once
all points
on the checklist can be answered with
yes
may
the GCU compact be handed over to the operator.