Troubleshooting by Remote Controller
SiE 00-07
126
Troubleshooting R-407C PLUS Series
Outdoor
Unit
J6
9
9
9
Malfunction of thermistor (R2T) for heat exchanger (loose
connection, disconnection, short circuit, failure)
J6
8
7
9
Malfunction of thermistor (R2T) for heat exchanger (loose
connection, disconnection, short circuit, failure)
JA
9
9
9
Malfunction of discharge pipe pressure sensor
JC
9
9
9
Malfunction of suction pipe pressure sensor
JH
8
7
9
Malfunction of oil temperature sensor
—
L0
9
9
9
Failure of inverter system
—
L4
9
9
9
Malfunction of inverter radiating fin temperature rise
L5
9
9
9
Inverter instantaneous over-current
L6
9
9
9
Compressor motor insulation defect, short circuit
—
L8
9
9
9
Inverter thermostat sensor, Compressor overload
L9
9
9
9
Inverter stall prevention, Compressor lock
LA
9
9
9
Malfunction of power unit
—
LC
9
9
9
Malfunction of transmission between inverter and control
PC board
System
P0
9
7
9
Gas depletion (heat build up)
—
P1
9
9
9
Inverter over-ripple protection
P4
9
9
9
Malfunction of inverter radiating fin temperature sensor
U0
8
7
9
Low pressure drop due to refrigerant shortage or electronic
expansion valve failure
U1
9
9
9
Negative phase / open phase
U2
9
9
9
Power supply insufficient or instantaneous failure
U4
9
9
9
Malfunction of transmission between indoor unit
U5
9
9
9
Malfunction of transmission between remote controller and
indoor unit
U5
7
8
7
Failure of remote controller PC board or setting during
control by remote controller
—
U7
9
9
9
Malfunction of transmission between indoor units
Malfunction of transmission between outdoor units,
malfunction of transmission between outdoor unit and ice
build-up heat unit
—
U7
8
7
9
Malfunction of transmission between outdoor units (cool/
heat unified, low noise)
U8
9
9
7
Malfunction of transmission between master and slave
remote controllers (malfunction of slave remote controller)
U9
9
9
9
Malfunction of transmission between indoor unit and
outdoor unit in same system
UA
9
9
9
Excessive number of indoor units
UC
8
8
8
Address duplication of central remote controller
UE
9
9
9
Malfunction of transmission between indoor unit and central
remote controller
UF
9
9
9
Refrigerant system not set, incompatible wiring / piping
UH
9
9
9
Malfunction of system, refrigerant system address
undefined
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Malfunction
code
Operation
lamp
Inspection
display
Unit No.
Malfunction contents
Page
Refered
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...