Test Operation
SiE 00-07
100
Test Operation R-407C PLUS Series
1.12.2 Wired Remote Controller – Heat Reclaim Ventilation <BRC301B61>
Setting procedure
1. In the Normal Mode, press the
button for more than 4 seconds to enter the Local Setting mode.
2. Using the
(Mode No. UP) and [Ventilation Volume] (Mode No. DOWN) buttons to select a
desired Mode No.
3. To set individual Heat Recraim Ventilation units in group control (select Mode Nos. 27 and 28 (Heat
Recraim Ventilation )), press the
button and choose the Unit No. to set. (This step is not
necessary in all group unit setting.)
4. Press the
UP button to select a Setting Switch No.
5. Press the
DOWN button to select a Setting Position No.
6. Press the
button once to enter the settings.
7. Depress the
button for about 1 second to return to the Normal Mode.
(Example)
When setting the filter sign time to "Filter Dirtiness - High" in all group unit setting, set the Mode No. to "17,"
Mode Setting No. to "0" and Setting Position No. to "02."
4
3
6
1, 7
5
2
Unit No.
Mode No.
Setting position No.
Field setting mode
Setting switch No.
(HL039)