Test Operation
SiE 00-07
86
Test Operation R-407C PLUS Series
1.4.3
Monitor Mode
After making sure the data is correct, push the RETURN button and return to No. 0, or push the
MODE button and return to setting mode 1.
16
4
32
8
2
1
MODE
TEST
L.N.O.P.
SEQ.
IND
MASTER SLAVE
START
H1P
H2P
H3P
H4P
H5P
H6P
H7P
MODE
To enter the monitor mode, push the MODE button when in setting mode 1.
RETURN
SET
SET
SET
The lower 4 digits indicate the setting in each of the frames
below.
The No. 1 cool/heat group address is expressed as a
binary number consisting of the lower 6 digits. (0 - 63)
In (1), the address is 010110 (binary number), which
translates to 16 + 4 + 2 = 22 (base 10 number). In other
words, the address is 22.
Tc (high pressure for heating)
High
Normal (factory set)
Low
Te (low pressure for cooling)
High
Normal (factory set)
Low
Defrost
(temperature setting for defrost)
Quick defrost
Normal (factory set)
Slow defrost
EMG
(emergency operation when
malfunction occurs)
ON
OF
Push the SET button and match with the LEDs No. 1 - 15, push the RETURN button,
and enter the data for each setting.
* Data such as addresses and number of units is expressed as binary numbers; the two
ways of expressing are as follows:
∗
See the following page for a list of the data for No. 1 - 16.
1
The number of terminal blocks for No. 12 and 13 is
expressed as an 8-digit binary number which is the
combination of four upper and four lower digits for No.
12 and 13 respectively. (0 - 128)
In (2), the address for No. 12 is 0101, the address for
No. 13 is 0110, and the combination of the two is
01010110 (binary number), which translates to 64 + 16
+ 4 + 2 = 86 (base 10 number). In other words, the
number of terminal blocks is 86.
64
16
No12
128
32
2
4
1
No13
8
2
No 0
RETURN
No 1
No 16
RETURN
(1 to 15 times)
C/H SELECT
(VF135)
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...