SiE 00-07
Specifications
Specifications R-407C PLUS Series
19
Concealed ceiling unit
Notes:
1 Nominal cooling capacities are based on the following conditions:
Return air temperature : 27˚C DB, 19˚C WB, Outdoor temperature : 35˚C DB
Equivalent ref. piping : 5m (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature : 20˚C DB, Outdoor temperature : 7˚C DB, 6˚C WB
Equivalent ref. piping : 5m (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Static external pressure is changeable to change over the connectors inside electrical box, this pressure
means “High static pressure-Standard”.
Daikin Europe model : FXYSP-KA7V1
More information can be found in the Technical Data book covering VRV systems
Model
FXYSP80KV1
FXYSP100KV1
FXYSP125KV1
Power Supply
1 phase 50Hz
220-240V
1 phase 50Hz
220-240V
1 phase 50Hz
220-240V
1 Cooling Capacity
kW
9.0
11.2
14.0
2 Heating Capacity
kW
10.0
12.5
16.0
Casing
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Dimensions: (H
×
W
×
D)
mm
300
×
1,400
×
800
300
×
1,400
×
800
300
×
1,400
×
800
Coil (Cross
Fin Coil)
Rows
×
Stages
×
Fin Pitch
mm
3
×
14
×
1.75
3
×
14
×
1.75
3
×
14
×
1.75
Face Area
m
²
0.338
0.338
0.338
Fan
Model
V1
3D18H2AH1V1
3D18H2AH1V1
3D18H2AG1V1
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor Output
×
Number
of Units
W
135
×
1
135
×
1
225
×
1
Air Flow Rate (H/L)
m
³
/min
27/20
28/20.5
38/28
4 External Static
Pressure
Pa
88-49
98-69
78-39
Drive
Direct Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Glass Fiber
Glass Fiber
Glass Fiber
Air Filter
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Piping
Connections
Liquid Pipes
9.5mm (Flare Connection)
9.5mm (Flare Connection)
9.5mm (Flare Connection)
Gas Pipes
15.9mm (Flare Connection)
19.1mm (Flare Connection)
19.1mm (Flare Connection)
Drain Pipe
(mm)
VP25 (External Dia. 32
Internal Dia. 25)
VP25 (External Dia. 32
Internal Dia. 25)
VP25 (External Dia. 32
Internal Dia. 25)
Weight
kg
51
51
52
Safety Devices
Fuse
Thermal Protector for Fan Motor
Fuse
Thermal Protector for Fan Motor
Fuse
Thermal Protector for Fan Motor
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Decoration
Panels
Model
BYBS125DJW1
BYBS125DJW1
BYBS125DJW1
Panel Color
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
Dimensions: (H
×
W
×
D)
mm
55
×
1,500
×
500
55
×
1,500
×
500
55
×
1,500
×
500
Weight
kg
6.5
6.5
6.5
Standard Accessories
Operation Manual, Installation Manual,
Paper Pattern for Installation, Drain
Hose, Clamp Metal, Insulation for
Fitting, Sealing Pads, Clamps, Screws,
Washers.
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
Conversion Formulae
kcal/h=kW
×
860
Btu/h=kW
×
3414
cfm=m
³
/min
×
35.3
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...