SiE 00-07
Troubleshooting
Troubleshooting R-407C PLUS Series
141
3.19
Outdoor Unit: Malfunction of Thermistor for Outdoor Air (R1T)
Remote Controller
Display
H9
Supposed Causes
Defect of thermistor (R1T) for outdoor air
Defect of outdoor unit PC board (A1P)
Troubleshooting
The alarm indicator is displayed when the fan only is being used also.
(VF045)
Resistance
is normal when
measured after
disconnecting the thermistor
(R1T) from the outdoor
unit PC board.
(3.5k
Ω
~
360k
Ω
)
Connector is
connected to X20A of outdoor
PC board (A1P).
Replace outdoor unit PC board A1P.
Connect the thermistor and turn on
again.
NO
NO
Replace the thermistor (R1T)
YES
YES