Test Operation
SiE 00-07
88
Test Operation R-407C PLUS Series
1.5
Cool / Heat Mode Selection
The R-407C VRV PLUS Series offers the following four cool/heat mode selections.
1. Setting of cool/heat by individual outdoor unit system by indoor unit remote controller
2. Setting of cool/heat by individual outdoor unit system by cool/heat selector
3. Setting of cool/heat by outdoor unit system group in accordance with group master outdoor unit by
indoor unit remote controller
4. Setting of cool/heat by outdoor unit system group in accordance with group master outdoor unit by cool/
heat selector
Each of these setting methods is explained in detail below.
(For 3 and 4 be sure to perform power supply reset after changing settings.)
1.5.1
Setting of Cool / Heat by Individual Outdoor Unit System by Indoor Unit Remote Controller
Doesn’t matter whether or not there is outdoor - outdoor unit wiring.
Set SS1 of the outdoor unit PCB to “IN / D UNIT” (factory set).
In setting mode 1, set cool/heat selection to “IND” (factory set).