Failure Diagnosis for Inverter System
Troubleshooting R-407C PLUS Series
157
4. Failure Diagnosis for Inverter System
4.1
Points of Diagnosis
The main causes for each malfunction code are given in the table below. (For details refer to the next page
and those following.)
: Failure is probable
: Failure is possible
: Failure is improbable
— : Failure is impossible
Malfunction
code
Contents of
malfunction
Location of failure
Point of diagnosis
Inverter
Compressor
Refrigerant
system
Outdoor
unit PC
board
Other
Field
cause
PC board
power unit
Other
L4
Radiator fin
temperature
rise
—
—
—
—
Is the intake port of
the radiator fin
clogged?
L5
Instantaneous
over-current
—
—
—
—
Inspect the
compressor.
L8
Electronic
thermostat
—
—
—
—
Inspection the
compressor and
refrigerant system.
L9
Stall
prevention
—
—
—
—
Inspection the
compressor and
refrigerant system.
LC
Malfunction of
transmission
between
inverter PC
board and
outdoor unit
PC board
—
—
—
—
Inspect the
connection
between the
inverter PC board
and outdoor unit PC
board. Next, inspect
the inverter PC
board.
U2
Abnormal
current/
voltage
—
—
—
•
Inspect the fuse
on the inverter PC
board.
•
Check the DC
voltage.
P1
Over-ripple
protection
—
—
—
—
•
Open phase
•
Current/voltage
imbalance
•
Defect of main
circuit wiring
P4
Defect of
radiator fin
temperature
sensor
—
—
—
—
—
Inspect the radiator
fin thermistor.
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...