SiE 00-07
Outline of Control (Indoor Unit)
Function R-407C PLUS Series
73
Heating
When heating, the hot air rises to the top of the room, resulting in the temperature being lower near the
floor where the occupants are. When controlling by body thermostat sensor only, the unit may therefore be
turned off by the thermostat before the lower part of the room reaches the preset temperature. The
temperature can be controlled so the lower part of the room where the occupants are doesn’t become cold
by widening the range in which thermostat sensor in remote controller can be used so that suction
temperature is higher than the preset temperature.
Ex: When heating
Assuming the preset temperature in the figure above is 24˚C, and the suction temperature has
changed from 18˚C to 28˚C (A
→
F):
(This example also assumes there are several other air conditioners, the VRV system is off, and that
temperature changes even when the thermostat sensor is off.)
Body thermostat sensor is used for temperatures from 18˚C to 25˚C (A
→
C).
Remote controller thermostat sensor is used for temperatures from 25˚C to 28˚C (C
→
E).
And, assuming suction temperature has changed from 28˚C to 18˚C (D
→
A):
Remote controller thermostat sensor is used for temperatures from 28˚C to 23˚C (D
→
B).
Body thermostat sensor is used for temperatures from 23˚C to 18˚C (B
→
A).
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...