INSTRUCTION MANUAL 

E2xC1LD2R & E2xC1LD2F Combined Sounder & Beacon 
For use in Hazardous Locations

 

 

 

E2XC1LD2F 

E2XC1LD2R 

1)  Product Table

 

 

 
Ensure the system power supply is capable of providing the maximum current required for all units. Review associated cable 
size, length and quantity of units on each circuit. 

 

2)  Warnings 

 DO NOT OPEN WHEN AN EXPLOSIVE 

ATMOSPHERE IS PRESENT 

 DO NOT OPEN WHEN ENERGISED 

 POTENTIAL ELECTROSTATIC CHARGING 

HAZARD - CLEAN ONLY WITH A DAMP 
CLOTH 

 HIGH VOLTAGE SHOCK HAZARD. WAIT 5 

MINUTES AFTER REMOVING POWER 
BEFORE OPENING THE ENCLOSURE 
 

Avertissement: 

 NE PAS OUVRIR UN PRESENCE 

D’ATMOSPHERE EXPLOSIVE 

 NE PAS OUVRIR ENERGIE 

 DANGER POTENTIEL CHARGE 

ÉLECTROSTATIQUE - NETTOYER 
UNIQUEMENT AVEC UN CHIFFON HUMIDE 

 HAUT TENSION, RISK DE CHOC. 

ATTENDEZ 5 MINUTES APRES AVOIR 
DEBRANCHE L’ALIMENTATION AVANT 
D’OUVRIR LA BOITIER 

 

3)  Rating & Marking Information 

 

3.1. ATEX / IECEx / UKEx certification 

The  E2xC1LD2  combined  alarm  horn  and  LED  beacon 
complies with the following standards: 

Standards 

EN IEC 60079-0:2018 / IEC60079-0:2017 (Ed 7): 

Explosive Atmospheres - Equipment. General Requirements 

EN IEC 60079-7:2015 +A1:2018 / IEC 60079-7:2018 (Ed. 5.1): 

Explosive Atmospheres - Equipment Protection by Increased 

Safety "e" 

EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2): 

Explosive Atmospheres - Equipment Dust Ignition Protection 
by Enclosure "t" 

Ratings 

E2XC1LD2 : 
 

Ex ec IIC Gc T3 Ta -20°C to +55°C 
Ex tc IIIC Dc T105°C Ta -20°C to +55°C 
Ex tc IIIC Dc T90°C Ta -20°C to +40C 

 
Certificate No. 

DEMKO 06ATEX 0421554X 
IECEx ULD 14.0012X 
UL21UKEX2135X

 

ATEX Mark, Equipment 
Group and Category: 

 

II 3G 
II 3D

 

CE Marking 
 

 

 

UKCA Marking 

 

 

 

Model 

Nom. 

Voltage 

Voltage Range 

Sounder 

 Current 

Beacon 
Current

 

E2xC1LD2FDC024 

E2xC1LD2RDC024 

24Vdc 

18-30Vdc 

284mA 

346mA 

E2xC1LD2FDC048 

E2xC1LD2RDC048 

48Vdc 

42-54Vdc 

146mA 

115mA 

E2xC1LD2FAC115 

E2xC1LD2RAC115 

115-120Vac 

50/60Hz 

N/- 10% 

104mA 

102.4mA 

E2xC1LD2FAC230 

E2xC1LD2RAC230 

220-230Vac 

50/60Hz 

N/- 10% 

54mA 

49.4mA 

The current levels shown above are for the tone resulting in max. current draw (tone 1 - 340Hz Continuous) 
Table 1: Electrical Ratings. 

Summary of Contents for E2xC1LD2F

Page 1: ...ating Marking Information 3 1 ATEX IECEx UKEx certification The E2xC1LD2 combined alarm horn and LED beacon complies with the following standards Standards EN IEC 60079 0 2018 IEC60079 0 2017 Ed 7 Exp...

Page 2: ...IC Dc T105 C Ta 20 C to 55 C Ex tc IIIC Dc T90 C Ta 20 C to 40 C Installation must be carried out in compliance with the Canadian Electric Code 4 Zones Gas Groups Category and Temperature Classificati...

Page 3: ...e E2x combined sounder beacon should be secured to any flat surface using the three 7mm fixing holes on the stainless steel U shaped mounting bracket See Figure 1 The required angle can be achieved by...

Page 4: ...tional area of 2 5mm Strip wires to 8mm Wires may also be fitted using ferrules Terminal screws on the sounder PCBA need to be tightened down with a tightening torque of 0 45 Nm 4 Lb in Terminal screw...

Page 5: ...ing Independent Beacon and Sounder Operation Only The resistor must be connected directly across the ve and ve terminals as shown in the following drawing Form the resistor legs as shown in Fig 9a rem...

Page 6: ...he equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and rec...

Page 7: ...400 2900Hz 50Hz Sweeping 25 Tone 5 Tone 29 1 1 1 0 1 0 800 1000Hz 50Hz Sweeping 24 Tone 5 Tone 6 0 1 1 0 1 0 800Hz 2Hz Intermittent 23 Tone 5 Tone 2 1 0 1 0 1 0 544Hz 0 875 sec Intermittent 22 Tone 5...

Page 8: ...HOWN ABOVE DRAWING TO BS8888 2000 GEOMETRIC TOLERANCES TO ISO1101 1983 LINEAR DIMENSIONAL TOLS ANGULAR DIMENSIONAL TOLS 05 08 2020 05 08 2020 DC E2XC1LD2 UNITS Line Monitoring Stage 1 Apply power to S...

Page 9: ...Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standar...

Page 10: ...e and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Page 11: ...on Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 6007...

Page 12: ...Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the marke...

Reviews: