Troubleshooting (Inverter)
Troubleshooting R-407C PLUS Series
163
5.5
Outdor Unit: Malfunction of Transmission Between Inverter and Control PC
Board
Remote Controller
Display
LC
Supposed Causes
Malfunction of connection between the inverter unit and outdoor unit PC board
Defect of outdoor unit PC board (transmission section)
Defect of inverter unit
Defect of noise filter (NF1)
Lock of phase on power supply during outdoor unit operation
External factor (Noise etc.)
Troubleshooting
(VF067)
The
transmission
wiring between the
outdoor unit PC board, sub board
and inverter unit is
disconnected.
YES
Fix the disconnection and turn on
again.
Connect transmission wiring and turn
on again.
NO
YES
The
microcomputer
monitor (green) on
the inverter unit
is blinking.
The voltage
between red and
white of CN on the inverter
unit is 220 ~ 240 V
(50Hz)
YES
Defect of outdoor PC board or defect of
inverter unit
Check the noise filter (Z1F) for
disconnection, and check the power
supply wiring or the inverter unit.
Replace inverter PC board.
When the LC malfunction occur again,
replace control PC board.
YES
The
microcomputer
monitor (green) on
sub board is
blinking.
NO
Check the sub board power and the
connector tightness.
NO
NO
YES
NO
Are X3A on
the outdoor unit PC
board, sub board and X3A on
the inverterunit connected
securely.
YES
Fix the power supply.
NO
Are the
power supply
voltage between each
phase right?
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...