Troubleshooting (Inverter)
SiE 00-07
166
Troubleshooting R-407C PLUS Series
5.8
Outdoor Unit: Malfunction of Inverter Radiating Fin Temperature Rise Sensor
Remote Controller
Display
P4
Supposed Causes
Defect of radiator fin temperature sensor
Defect of inverter unit
Troubleshooting
(VF070)
After resetting, restart.
YES
YES
Is the resistance
of thermistor correct?
Is the resetting possible?
Replace radiation fin thermistor.
Measure the resistance of
radiation fin thermistor.
NO
Replace inverter PC board.
NO