Troubleshooting
SiE 00-07
150
Troubleshooting R-407C PLUS Series
3.28
Malfunction of Transmission Between Remote Controller and Indoor Unit
Remote Controller
Display
U5
Supposed Causes
Malfunction of indoor unit remote controller transmission
Connection of two main remote controllers (when using 2 remote controllers)
Defect of indoor unit PC board
Defect of remote controller PC board
Malfunction of transmission caused by noise
Troubleshooting
(VF055)
NO
YES
YES
NO
Replace indoor unit PC board.
Set one remote controller to
"SLAVE"; turn the power supply off
once and then back on.
There is possibility of malfunction
caused by noise. Check the
surrounding area and turn on
again.
NO
NO
Using
2-remote controllers
control.
All indoor
PC board microcomputer
monitors blink.
YES
Multi-core
cable is used for the indoor
unit remote controller
transmission
wiring.
Operation
returns to normal when the
power is turned off
momentarily.
YES
YES
SS1
of both remote controllers is set
to "MASTER."
NO
Switch to double-core independent
cable. replacement
Defect of remote controller PC
board or indoor unit PC board.
Replace whichever is defective.
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...