SiBE01-829
Troubleshooting
Service Diagnosis
55
4. Troubleshooting
4.1
Error Codes
and Description
★
: Displayed only when system-down occurs.
Code
Description
Reference
Page
System
00
Normal
—
U0
Insufficient gas
65
UA
Hardware error (tact switch pin short)
64
Indoor
Unit
A1
Indoor unit PCB abnormality
56
A5
Freeze-up protection control, high pressure control or indoor heat
exchanger thermistor abnormality
57
A6
Fan motor or related abnormality (AC motor)
59
C4
Heat exchanger thermistor abnormality
60
C9
Room temperature thermistor abnormality
60
Outdoor
Unit
F6
High pressure control in cooling or outdoor heat exchanger
thermistor abnormality
62
J6
Heat exchanger thermistor or related abnormality
64