Functions
SiBE01-829
16
Functions and Control
1.3
Thermostat Control
Thermostat control is based on the difference between the room temperature and the setpoint.
Cooling
Thermostat OFF: Room temperature – setpoint
≤ −
1
°
C
Thermostat ON : Room temperature – setpoint
≥
+1.5
°
C
Heating
Thermostat OFF: Room temperature – setpoint
≥
+3.5
°
C
Thermostat ON : Room temperature – setpoint
≤
+1
°
C
OFF
ON
Room temperature – setpoint
(R8488)
+1.5˚C
–1˚C
OFF
OFF
ON
ON
Room temperature – setpoint
(R8489)
+3.5˚C
+1˚C