Functions
SiBE01-829
18
Functions and Control
1.5
Programme Dry Function
Outline
Programme dry function removes humidity while preventing the room temperature from
lowering.
Since the microcomputer controls airflow rate, the fan adjustment buttons are inoperable in this
mode.
Details of the
Control
During the first 12 minutes of the DRY mode run from:
1. After operation halt for 2 hours or more or
2. Mode change from HEAT, FAN or AUTO HEAT
DRY mode must run under cool mode with AUTO indoor fan for 12 minutes or until
room temp. < set temp. – 1°C.
After this, the DRY mode may run under either Zone A, B, C or D as below:
1. If room temp. – set temp. > 2°C, the operation is in Zone A
ZONE A
2. If 0°C < room temp. – set temp. < 1°C, then the operation is in Zone B.
ZONE B
3. If 1°C < set temp. – room temp. < 2°C, then the operation is in Zone C.
ZONE C
12 min.
ON
OFF
ON
OFF
Compressor
L tap
Time
Time
(R8491)
Compressor
L tap
ON
OFF
ON
OFF
8 min.
4 min.
30 sec.
30 sec.
(R8492)
Compressor
L tap
ON
OFF
ON
OFF
6 min.
6 min.
30 sec.
30 sec.
(R8493)
Summary of Contents for FTYN25GXV1B
Page 1: ...SiBE01 829 Applied Models Non Inverter Pair Heat Pump SPLIT Pair Wall Mounted Type G Series...
Page 11: ...Introduction SiBE01 829 x...
Page 12: ...SiBE01 829 List of Function 1 Part 1 List of Function 1 Functions 2...
Page 15: ...Functions SiBE01 829 4 List of Function...
Page 16: ...SiBE01 829 Specifications 5 Part 2 Specifications 1 Specifications 6...
Page 19: ...Specifications SiBE01 829 8 Specifications...
Page 81: ...Check SiBE01 829 70 Service Diagnosis...
Page 86: ...Others SiBE01 829 108 Others...
Page 92: ...Wiring Diagrams SiBE01 829 114 Appendix...