Troubleshooting
SiBE01-829
64
Service Diagnosis
4.7
Hardware Error (Tact Switch Pin Short)
Remote
Controller
Display
UA
Method of
Malfunction
Detection
The supply power is detected for its requirement (different from pair type and multi type) by the
indoor / outdoor transmission signal.
Malfunction
Decision
Conditions
The pair type and multi type are interconnected.
Supposed
Causes
Wrong models interconnected
Wrong indoor unit PCB mounted
Indoor unit PCB defective
Wrong outdoor unit PCB mounted or defective
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check the indoor and outdoor unit
model numbers.
(R7342)
YES
NO
NO
YES
Check the code numbers
(2P01234, for example) of the
indoor and outdoor unit PCB with
the Parts List.
Match the compatible
models.
Replace the indoor unit
PCB (1) (or the outdoor unit
PCB).
Change for the specified
PCB (1) or (2).
Matched compatibly?
Indoor unit and
outdoor unit matched?
Summary of Contents for FTYN25GXV1B
Page 1: ...SiBE01 829 Applied Models Non Inverter Pair Heat Pump SPLIT Pair Wall Mounted Type G Series...
Page 11: ...Introduction SiBE01 829 x...
Page 12: ...SiBE01 829 List of Function 1 Part 1 List of Function 1 Functions 2...
Page 15: ...Functions SiBE01 829 4 List of Function...
Page 16: ...SiBE01 829 Specifications 5 Part 2 Specifications 1 Specifications 6...
Page 19: ...Specifications SiBE01 829 8 Specifications...
Page 81: ...Check SiBE01 829 70 Service Diagnosis...
Page 86: ...Others SiBE01 829 108 Others...
Page 92: ...Wiring Diagrams SiBE01 829 114 Appendix...