Troubleshooting
Service Diagnosis
111
Troubleshooting
Check No.15
Refer to P.120
Check No.17
Refer to P.123
Check No.18
Refer to P.124
Check No.22
Refer to P.126
(R14446)
Caution
NO
YES
NO
YES
NO
YES
YES
NO
NO
YES
YES
NO
∗
An output overcurrent may result from wrong internal wiring. If the system is interrupted by an output
overcurrent after the wires have been disconnected and reconnected for part replacement, check the
wiring again.
Keep on using as it is.
Check the connectors and
other components.
Fully open the stop valve.
Correct the power supply.
Replace the compressor.
Correct the power supply
or replace the outdoor unit
PCB.
Replace the outdoor unit
PCB.
∗
Inverter checker
Part No.: 1225477
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Stop valve fully open?
Error again?
Check No.15
Check with the inverter checker (
∗
).
Any LED off?
Check the supply voltage.
Voltage as rated?
Monitor the supply voltage,
discharge and suction pressures,
and other factors for a long term.
Possible causes
∗
Momentary fall of supply voltage
∗
Compressor overload
∗
Short circuit
Check No. 17
Check the installation condition.
Turn off the power and turn it on
again to start the system. See if the
same error occurs.
Turn off the power and disconnect
the harnesses U, V, and W.
Check No. 22
Check the
power module.
Normal?
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Short circuit or
wire breakage between
compressor's coil
phases?
Check No. 18
Check the discharge pressure.