SiUS041111
Outdoor Unit: 09/12 Class
Removal Procedure
173
3.3
Removal of Electrical Box / PCB
Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
1. Remove the right side
panel.
Preparation
Remove the panels
according to the “Removal of
Outer Panels”.
1
Release the outdoor
temperature thermistor
from the outdoor heat
exchanger.
2
Remove the screw on
the rear side of the right
side panel.
(R14693)
Outdoor
temperature
thermistor
Right
side
panel
(R14692)