SiUS041111
Troubleshooting
Service Diagnosis
93
4.12 Input Overcurrent Detection
Remote
Controller
Display
E8
Method of
Malfunction
Detection
An input overcurrent is detected by checking the input current value with the compressor running.
Malfunction
Decision
Conditions
The current exceeds about 15 A for 2.5 seconds with the compressor running.
(The upper limit of the current decreases when the outdoor temperature exceeds a certain
level.)
Supposed
Causes
Defective compressor
Defective outdoor unit PCB
Short circuit
Troubleshooting
Check No.15
Refer to P.120
Check No.17
Refer to P.123
Check No.18
Refer to P.124
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
∗
An input overcurrent may result from wrong internal wiring. If the system is interrupted by an input
overcurrent after the wires have been disconnected and reconnected for part replacement, check the
wiring again.
(R14440)
NO
YES
YES
NO
Replace the outdoor unit
PCB.
Correct the power supply
or replace the outdoor unit
PCB.
∗
Inverter checker
Part No.: 1225477
Check No. 17
Check the installation condition.
Start operation and measure the
input current.
Check No.15
Check with the inverter checker (
∗
).
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Check No. 18
Check the discharge pressure.
Input current flowing
above its stop level?
Turn off the power and disconnect
the harnesses U, V, and W.
Any LED off?