Outdoor Unit: 15/18/24 Class
SiUS041111
206
Removal Procedure
4.4
Removal of PCBs
Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
1. Remove the main PCB.
[S12]: for [HL4] [HN4] on filter PCB
1
Disconnect the
connector [S12] and
pull out the clamp.
2
Disconnect the
connector [S10].
[S10]: for [S11] on filter PCB
3
Disconnect the
connectors [HN3]
[HL3].
[HL3] [HN3]: for [HL2] [HN2] on
filter PCB
(R14322)
[S12]
Main PCB
(R14323)
[S10]
[HN3]
[HL3]
(R14324)