Troubleshooting - Outdoor Unit Related
Si18-201
288
Service Diagnosis
3.3.25
Stall Prevention
Outdoor Unit
Indication
L9
Method of
Malfunction
Detection
Stall prevention system error is detected using the compressor's output current.
Malfunction
Decision
Conditions
#
When the compressor's output current of 33A or higher continued for 0.3 seconds and peak
current reached to 65A or higher
#
When the compressor's output current of 33A or higher continued for 5 seconds
#
When failing to changeover the position detecting function
"
When a stall prevention error is generated 4 times, the system shuts down.
(The 4-time counter resets itself when no outdoor unit abnormality occurs within 60-minute
cumulative time after the error generation.)
Supposed
Causes
"
Faulty compressor
"
Overcurrent due to faulty PC board
"
Incorrect detection due to faulty PC board
"
Overload due to incorrect installation
"
Overload at time of starting including high differential pressure start, etc.
Troubleshooting
Check No.5
Refer to P.302
Check No.6
Refer to P.303
Check No.7
Refer to P.304
Check No.1
Refer to P.300
Check No.2
Refer to P.300
YES
Faulty pressure balance
Apply required remedy
subject to the case.
Replace compressor.
Apply required remedy
subject to the case.
Apply required remedy
subject to the case.
Is the
differential pressure
between higher and lower
pressure prior to starting
2kgf/cm²?
(MF044)
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check No. 5
Main circuit wiring
connection check
Check No. 6
Power transistor check
Check No. 7
Power transistor output check
Check No. 1
Installation conditions check
OK
Check No. 2
Discharge pressure check
OK
Is the
compressor short-circuited or
ungrounded?
YES
NO
Summary of Contents for FTX25JVEA9
Page 9: ...Si18 201 viii Table of Contents...
Page 71: ...Specifications Si18 201 58 Specifications...
Page 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ...
Page 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ...
Page 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H...
Page 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J...
Page 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC...
Page 214: ...Si18 201 Remote Controller Operations 201...
Page 216: ...Si18 201 Remote Controller Operations 203...
Page 217: ...Remote Controller Si18 201 204 Operations...
Page 237: ...Method of Field Set Si18 201 224 Operating Test...
Page 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249...
Page 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C...
Page 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9...
Page 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION...
Page 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C...