Method of Field Set
Si18-201
218
Operating Test
After Setting
Stick the Unit No. label at decoration panel air discharge outlet as well as on the back of the
wireless remote controller.
PRECAUTIONS
Set the Unit No. of the receiver and the wireless remote controller to be equal. If the setting
differs, the signal from the remote controller cannot be transmitted.
1. Do not use any settings not listed in the table.
2. For group control with a wireless remote controller, initial settings for all the indoor units of
the group are equal. (For group control, refer to the installation manual attached to the
indoor unit for group control.)
Fan Speed OFF when Thermostat is OFF
When the cool/heat thermostat is OFF, you can stop the indoor unit fan by switching the setting
to “Fan OFF.”
∗
Used as a countermeasure against odor for barber shops and restaurants.
Setting Table
Ultra-Long-Life Filter Sign Setting
When a Ultra-long-life filter is installed, the filter sign timer setting must be changed.
Setting Table
Mode No.
First Code No.
Second Code No.
Setting
11(21)
2
01
—
02
Fan OFF
Mode No.
Setting Switch No.
Setting Position No.
Setting
10 (20)
1
01
Long-Life Filter
02
Ultra-Long-Life Filter (1)
03
Ultra-Long-Life Filter (2)
Summary of Contents for FTX25JVEA9
Page 9: ...Si18 201 viii Table of Contents...
Page 71: ...Specifications Si18 201 58 Specifications...
Page 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ...
Page 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ...
Page 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H...
Page 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J...
Page 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC...
Page 214: ...Si18 201 Remote Controller Operations 201...
Page 216: ...Si18 201 Remote Controller Operations 203...
Page 217: ...Remote Controller Si18 201 204 Operations...
Page 237: ...Method of Field Set Si18 201 224 Operating Test...
Page 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249...
Page 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C...
Page 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9...
Page 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION...
Page 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C...