System control
Si18-201
140
Main Functions
3.22
PI Control
Outline
Based on the
∆
D signal, MAX
α
of the command frequency is monitored every 20 seconds, and
PI control is provided accordingly. (Coefficient of PI control varies for each S value.)
P Control
At every sampling time TFSMP, the maximum value (MAX
α
) of
α
value is calculated, and if the
result differs from the previous value, the frequency is changed according to the amount of
fluctuation.
When the previous MAX
α
is MAX
α
1 and the newest MAX
α
is MAX
α
0, the upper-limit value of
MAX
α
is
MAX_ALFA_MX(9).
Operating frequency operating amount
∆
F:
∆
F = KP × (MAX
α
0 - MAX
α
1)
P control is prohibited under the following conditions
(Equation (A))
MAX_ALFA_P1(3)
≤
MAX
α
0
≤
MAX_ALFA_P2(5)
MAX_ALFA_P1(3)
≤
MAX
α
1
≤
MAX_ALFA_P2(5)
P control is prohibited under left condition.
I Control
When the
∆
D signal does not change for the specified time, the frequency is increased or
decreased according to the MAX
α
value to set the MAX
α
value to the specified level.
When MAX
α
value is small
→
Frequency is decreased
When MAX
α
value is large
→
Frequency is increased
When MAX
α
at TFSMP(20) timer time-over is MAX
α
0:
If MAX
α
0
≥
MAX_ALFA_12(6)
When frequency does not change for TFSMP × M(120 sec)
Operating frequency operating amount
∆
F is set to
∆
F = KI × (MAX
α
0 - MAX_ALFA_MK(3))
If MAX
α
0
≤
MAX_ALFA_11(2)
Operating frequency is decreased at every TFSMP(20 sec)
Operating frequency operating amount
∆
F is set to
∆
F = -KI × BI(1)
I control is prohibited when MAX_ALFA_11(2) < MAX
α
0 < MAX_ALFA_12(6)
Summary of Contents for FTX25JVEA9
Page 9: ...Si18 201 viii Table of Contents...
Page 71: ...Specifications Si18 201 58 Specifications...
Page 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ...
Page 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ...
Page 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H...
Page 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J...
Page 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC...
Page 214: ...Si18 201 Remote Controller Operations 201...
Page 216: ...Si18 201 Remote Controller Operations 203...
Page 217: ...Remote Controller Si18 201 204 Operations...
Page 237: ...Method of Field Set Si18 201 224 Operating Test...
Page 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249...
Page 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C...
Page 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9...
Page 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION...
Page 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C...