Si18-201
System control
Main Functions
117
3.6.3 Determination of Initial Frequency
Initial frequency setting (determination of initial operating frequency based on S value and
∆
D
signal (
α
value))
Outline
When the compressor starts and when a change occurs in the conditions such as change of
room unit operations, the sum of the maximum
α
value (MAX
α
) of each H/U unit, the total of S
values of operating indoor units (
Σ
SU) and the total of S values of non-operating room units
(
Σ
ST) is used for the frequency initialization.
(Addition of non-operating room unit correction to S value classification)
Non-operating room unit refers to an indoor unit with thermostat OFF.
To ensure appropriate capacity supply in accordance with outside temperature, correction is
provided based on the outside temperature.
Furthermore, for improved startup in heating cold start, frequency correction is provided based
on the detection of cold start or hot start (change in the number of rooms) using the discharge
pipe temperature.
Description
Determination of S value classification
The sum of S values sent form each BP unit of operating rooms (
Σ
Su) and non-operating rooms
(
Σ
ST) are used to determine the S value of outdoor unit (system).
For cooling:
Σ
S=
Σ
Su
For heating:
Σ
S=
Σ
Su + 0.25 ~
Σ
ST
When S value changes in above case, the initial frequency is determined according to the
following matrix and set as FINI 1.
Note
No change is made in
Σ
S during defrost control (FD = 1).
The frequency obtained by substituting FINI 1, outside air temperature and discharge pipe
temperature in the following equation is set as command frequency FSR.
Whereas,
Discharge pipe temperature DO
≥
45°C: KFIDO = 1
Discharge pipe temperature DO < 45°C: KFIDO = 1.4
S value : Frequency constant
Σ
S : Total of S value
Summary of Contents for FTX25JVEA9
Page 9: ...Si18 201 viii Table of Contents...
Page 71: ...Specifications Si18 201 58 Specifications...
Page 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ...
Page 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ...
Page 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H...
Page 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J...
Page 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC...
Page 214: ...Si18 201 Remote Controller Operations 201...
Page 216: ...Si18 201 Remote Controller Operations 203...
Page 217: ...Remote Controller Si18 201 204 Operations...
Page 237: ...Method of Field Set Si18 201 224 Operating Test...
Page 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249...
Page 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C...
Page 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9...
Page 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION...
Page 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C...