Si18-201
Troubleshooting - Outdoor Unit Related
Service Diagnosis
263
3.3
Troubleshooting Detail
3.3.1
High Pressure Malfunction
Outdoor Unit
Indication
E3
Method of
Malfunction
Detection
Continuity of the high pressure switch is detected by the safety device circuitry.
Malfunction
Decision
Conditions
When HPS malfunction is generated 4 times, the system shuts down.
(The 4-time counter resets itself when no outdoor unit abnormality occurs within 60-minute
cumulative time after the error generation.)
Supposed
Causes
"
Faulty high pressure switch
"
Disconnection of high pressure switch's harness
"
Faulty connectors connection of high pressure switch
"
Dirty indoor unit heat exchanger
"
Faulty outdoor unit fan
"
Over-charged with refrigerant
"
Motorized valve clogged
Troubleshooting
Check No.1
Refer to P.300
Check No.2
Refer to P.300
Check No.3
Refer to P.301
YES
To E7 Flow Chart
Connect correctly.
Replace HPS without
continuity.
Apply required remedy
subject to the case.
Replace motorized valve if
faulty.
Replace control PC board.
Replace motorized valve if
faulty.
Replace control PC board.
Does the outdoor
unit fan rotate?
Does the warm air
come out?
(MF020)
Check No.1
Check the installation
conditions.
It comes out.
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is HPS correctly
connected?
Turn the power supply off and
check the following after letting the
compressor rest for 10 minutes.
Does the HPS have
continuity?
NO
Check No. 2
Pressure check
Check No. 1
Installation conditions check
YES
Cooling?
Heating
Check No. 3
Motorized valve EVL
check
OK
Check No. 3
Motorized valve EVn
check
OK
Summary of Contents for FTX25JVEA9
Page 9: ...Si18 201 viii Table of Contents...
Page 71: ...Specifications Si18 201 58 Specifications...
Page 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ...
Page 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ...
Page 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H...
Page 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J...
Page 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC...
Page 214: ...Si18 201 Remote Controller Operations 201...
Page 216: ...Si18 201 Remote Controller Operations 203...
Page 217: ...Remote Controller Si18 201 204 Operations...
Page 237: ...Method of Field Set Si18 201 224 Operating Test...
Page 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249...
Page 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C...
Page 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9...
Page 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION...
Page 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C...