Si18-201
Troubleshooting - Split Type Indoor Unit
Service Diagnosis
241
Troubleshooting
Check the varistor of the
indoor unit PCB.
Check the supply voltage.
Does the power
supply have the rated
voltage?
NO
NO
NO
Is it damaged?
Is there conductivity?
Is there conductivity?
Check the thermal fuse of the
terminal board.
Check the fuse of the indoor
unit PCB.
Is the connection proper?
Check the connection wire
contact at the terminal board.
NO
NO
YES
YES
YES
YES
Check the power supply, and
correct it if not proper.
Replace the varistor.
Replace the fuse.
Replace the thermal fuse of
the terminal board.
Replace the terminal board
and thermal fuse.
(MF007)
To next page
1
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for FTX25JVEA9
Page 9: ...Si18 201 viii Table of Contents...
Page 71: ...Specifications Si18 201 58 Specifications...
Page 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ...
Page 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ...
Page 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H...
Page 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J...
Page 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC...
Page 214: ...Si18 201 Remote Controller Operations 201...
Page 216: ...Si18 201 Remote Controller Operations 203...
Page 217: ...Remote Controller Si18 201 204 Operations...
Page 237: ...Method of Field Set Si18 201 224 Operating Test...
Page 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249...
Page 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C...
Page 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9...
Page 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION...
Page 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C...