1
Water quality
The table below contains the required water quality specifications.
Evaporator water
Heated water (low temperature)
Tendency if out of
criteria
Circulating
water (< 20°C)
Supply water
Circulating water
(20°C-60°C)
Supply water
Items to be checked
pH
at 25°C
6.8~8.0
6.8~8.0
7.0~8.0
7.0~8.0
Cor scale
Electrical conductivity
mS/m
(at 25°C)
< 40
< 30
< 30
< 30
Cor scale
Chloride ion
mg Cl
-
/l
< 50
< 50
< 50
< 50
Corrosion
Sulphate ion
mg SO
4
2-
/l
< 50
< 50
< 50
< 50
Corrosion
M-alkalinity (pH 4.8)
mg CaCO
3
/l
< 50
< 50
< 50
< 50
Scale
Total hardness
mg CaCO
3
/l
< 70
< 70
< 70
< 70
Scale
Calcium hardness
mg CaCO
3
/l
< 50
< 50
< 50
< 50
Scale
Silica ion
mg SiO
2
/l
< 30
< 30
< 30
< 30
Scale
Items to be referred to
Iron
mg Fe/l
< 1.0
< 0.3
< 1.0
< 0.3
Cor scale
Copper
mg Cu/l
< 1.0
< 0.1
< 1.0
< 0.1
Corrosion
Sulphide ion
mg S
2-
/l
Not detectable
Not detectable
Not detectable
Not detectable
Corrosion
Ammonium ion
mg NH
4
+
/l
< 1.0
< 0.1
< 0.3
< 0.1
Corrosion
Remaining chloride
mg Cl/l
< 0.3
< 0.3
< 0.25
< 0.3
Corrosion
Free carbide
mg CO
2
/l
< 4.0
< 4.0
< 0.4
< 4.0
Corrosion
Stability index
–
–
–
–
Cor scale
Summary of Contents for EUWL KZW1 Series
Page 1: ......
Page 2: ......
Page 8: ...Introduction ESIE 0303 vi 3 1 4 5 ...
Page 10: ...ESIE 0303 1 2 Part 1 System Outline 3 1 1 5 ...
Page 50: ...Piping Layout ESIE 0303 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 60: ...Wiring Layout ESIE 0303 1 52 Part 1 System Outline 3 1 1 4 5 ...
Page 61: ...ESIE 0302 Wiring Layout Part 1 System Outline 1 53 3 6 Wiring Diagram Wiring diagram ...
Page 62: ...Wiring Layout ESIE 0302 1 54 Part 1 System Outline ...
Page 64: ...ESIE 0303 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 84: ...ESIE 0303 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 87: ...ESIE 0303 Inputs and Outputs Overview Part 3 Troubleshooting 3 5 3 3 4 5 1 ...
Page 88: ...Inputs and Outputs Overview ESIE 0303 3 6 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 94: ...Malfunction Indications and Safeties Overview ESIE 0303 3 12 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 100: ...Checking the Inputs and Outputs ESIE 0303 3 18 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 112: ...Troubleshooting ESIE 0303 3 30 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 114: ...ESIE 0303 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 130: ...ESIE 0303 5 2 Part 5 Maintenance 3 1 5 ...
Page 139: ...ESIE 0303 Index 3 3 4 5 1 Wiring Diagram k 1 53 ...
Page 140: ...ESIE 0303 4 Index 3 1 4 5 ...