![Daikin EUWL KZW1 Series Service Manual Download Page 109](http://html1.mh-extra.com/html/daikin/euwl-kzw1-series/euwl-kzw1-series_service-manual_3565814109.webp)
ESIE-0303
Troubleshooting
3–27
3
3
4
5
1
Fans
The table below contains the settings of the fans.
Anti-freeze and
supporting heaters
The table below contains the settings of the anti-freeze and the supporting heaters.
Alarm
The table below contains the settings of the alarm.
Code
Parameter
Function
EUW(L)5-24KZW1
Read/
write
f1
Factory
Are there any fans?
0
r/w
Code
Parameter
Function
EUW5-24KZW1
EUWL5-24KZW1
Read/
write
a1
Factory
Anti-freeze alarm set
point
Standard
4°C
r/w
ZL option
-11.5°C
ZH option
-6.5°C
a2
Factory
Anti-freeze alarm hysteresis
3.5°C
a3
Factory
Bypass time for anti-freeze alarm
0 s
a7
Factory
Limit anti-freeze alarm set
-15°C
Code
Parameter
Function
EUW5-24KZW1
EUWL5-24KZW1
Read/
write
p1
Factory
Flow-start timer
20 s
r/w
p2
Factory
Flow-stop timer
5 s
p3
Factory
LP bypass timer
60 s
p4
User
Buzzer ON time
1 min.
p5
Factory
Reset of alarms
0
p8
Factory
Selection of digital input ID1
1
p9
Factory
Selection of digital input ID2
8
pa
Factory
LP alarm when the compr. is OFF
0
pb
Factory
High temperature alarm set
90°C
pv
Factory
High temperature alarm delayed at
start-up
30 min.
Summary of Contents for EUWL KZW1 Series
Page 1: ......
Page 2: ......
Page 8: ...Introduction ESIE 0303 vi 3 1 4 5 ...
Page 10: ...ESIE 0303 1 2 Part 1 System Outline 3 1 1 5 ...
Page 50: ...Piping Layout ESIE 0303 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 60: ...Wiring Layout ESIE 0303 1 52 Part 1 System Outline 3 1 1 4 5 ...
Page 61: ...ESIE 0302 Wiring Layout Part 1 System Outline 1 53 3 6 Wiring Diagram Wiring diagram ...
Page 62: ...Wiring Layout ESIE 0302 1 54 Part 1 System Outline ...
Page 64: ...ESIE 0303 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 84: ...ESIE 0303 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 87: ...ESIE 0303 Inputs and Outputs Overview Part 3 Troubleshooting 3 5 3 3 4 5 1 ...
Page 88: ...Inputs and Outputs Overview ESIE 0303 3 6 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 94: ...Malfunction Indications and Safeties Overview ESIE 0303 3 12 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 100: ...Checking the Inputs and Outputs ESIE 0303 3 18 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 112: ...Troubleshooting ESIE 0303 3 30 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 114: ...ESIE 0303 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 130: ...ESIE 0303 5 2 Part 5 Maintenance 3 1 5 ...
Page 139: ...ESIE 0303 Index 3 3 4 5 1 Wiring Diagram k 1 53 ...
Page 140: ...ESIE 0303 4 Index 3 1 4 5 ...