Malfunction Indications and Safeties Overview
ESIE-0303
3–8
3
1
3
4
5
2.2
Malfunction Indications Overview
Alarm and warning
codes
The following alarm and warning codes can appear on the screen:
What happens in
the event of an
alarm or a warning
In the event of an alarm or a warning, the following happens:
Code
Description
Alarm or
warning
Reset
See page
a1
The anti-freeze alarm has been activated.
Alarm
Manual
e1
NTC probe used to measure the evaporator inlet water temperature is
defective.
Alarm
Automatic
e2
NTC probe used to measure the evaporator outlet water temperature is
defective.
Alarm
Automatic
e3
NTC probe used to measure the condenser inlet water temperature is
defective.
Alarm
Automatic
ee
/
ep
EEPROM on the digital controller inside the unit is defective.
Alarm
Automatic
fl
No water flow for:
■
15 s after the pump was started, or
■
5 s while the compressor is active.
Alarm
Manual
—
h1
The high-pressure switch, the discharge thermal protection or the over-
current protection of the compressor motor is activated .
Alarm
Manual
—
l1
The low-pressure switch is activated.
Alarm
Manual
—
n1
The compressor requires maintenance. The total running hours of the
compressor (direct parameter
c9
) has exceeded the setting of the
timer threshold for maintenance warning (user parameter
cb
—see
"How to access the parameters" on page 2–17).
Warning
Manual
n2
The compressor requires maintenance. The total running hours of the
compressor (direct parameter
ca
) has exceeded the setting of the
timer threshold for maintenance warning (user parameter
cb
—see
"How to access the parameters" on page 2–17).
Warning
Manual
fl h1
The reverse phase protector has been activated.
Alarm
Automatic
—
e0
Voltage is too high.
Warning
Automatic
—
ei
Voltage is too low.
Warning
Automatic
—
el
Noise of power supply
Warning
Automatic
—
Alarm
Warning
■
The unit is shut down.
■
The buzzer is activated.
■
The alarm relay is energized.
■
The display starts flashing, alternately showing the
alarm code(s) and the inlet water temperature.
The display starts flashing, alternately
showing the warning code and the inlet
water temperature.
Summary of Contents for EUWL KZW1 Series
Page 1: ......
Page 2: ......
Page 8: ...Introduction ESIE 0303 vi 3 1 4 5 ...
Page 10: ...ESIE 0303 1 2 Part 1 System Outline 3 1 1 5 ...
Page 50: ...Piping Layout ESIE 0303 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 60: ...Wiring Layout ESIE 0303 1 52 Part 1 System Outline 3 1 1 4 5 ...
Page 61: ...ESIE 0302 Wiring Layout Part 1 System Outline 1 53 3 6 Wiring Diagram Wiring diagram ...
Page 62: ...Wiring Layout ESIE 0302 1 54 Part 1 System Outline ...
Page 64: ...ESIE 0303 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 84: ...ESIE 0303 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 87: ...ESIE 0303 Inputs and Outputs Overview Part 3 Troubleshooting 3 5 3 3 4 5 1 ...
Page 88: ...Inputs and Outputs Overview ESIE 0303 3 6 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 94: ...Malfunction Indications and Safeties Overview ESIE 0303 3 12 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 100: ...Checking the Inputs and Outputs ESIE 0303 3 18 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 112: ...Troubleshooting ESIE 0303 3 30 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 114: ...ESIE 0303 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 130: ...ESIE 0303 5 2 Part 5 Maintenance 3 1 5 ...
Page 139: ...ESIE 0303 Index 3 3 4 5 1 Wiring Diagram k 1 53 ...
Page 140: ...ESIE 0303 4 Index 3 1 4 5 ...