ESIE-0303
The Digital Controller: EUW5-24KZW1 and EUWL5-24KZW1
Part 2 – Functional Description
2–17
3
2
4
5
1
2.5
Settings: Direct and User Parameters
Direct and user
parameters
The table below describes the direct and user parameters.
How to access the
parameters
To access the parameters, proceed as follows:
Overview of the
parameters
The table below contains an overview of all the parameters. Each parameter is defined by a code and
a value.
Parameters
Description
Example
Direct
Are used for the daily usage of
the unit.
■
To set the cooling temperature set point.
■
To read the operational information.
User
Provide advanced features.
Remote control
To access the… parameters
Press 5 s on…
A password is…
Direct
s
Not required.
Direct and user
p
Required. Use
22
as password.
Code
Description
Type
Default Value
Limit values
Step
value
EUW5-24KZW1 and
EUWL5-24KZW1
:d
Measurement unit (°C or °F)
User
0°C
0 or 1
1
r1
Cooling temperature set point
Standard
Direct
12.0°C
8.0 to 25.0°C
0.1°C
ZL option
-7.0 to 25.0°C
ZH option
-2.0 to 25.0°C
r2
Cooling temperature difference
Direct
3.0°C
0.3 to 19.9°C
0.1°C
r3
Heating temperature set point
Standard
Direct
—
15.0 to
48.0°C
(inlet water
temperature)
0.1°C
ZL option
ZH option
r4
Heating temperature difference
Direct
—
0.3 to 19.9°C
0.1°C
c6
Time delay at start-up
User
0 s
0 to 150 s
1 s
c7
Time delay between the pump start-up and the
compressor start-up
User
15 s
0 to 150 s
1 s
c8
Time delay between the pump shutdown and the
compressor shutdown
User
0 min
0 min to
150 min
1 min
c9
(1)
Total running hours of the
compressor 1
Direct
Read-only
—
1 h
ca
(1)
Total running hours of the
compressor 2
Direct
Read-only
—
1 h
cb
Maintenance threshold of c9
User
0 (Read-only)
0 to 10000 h
100 h
cv
(1)
Total running hours of the pump
Direct
Read-only
—
—
Summary of Contents for EUWL KZW1 Series
Page 1: ......
Page 2: ......
Page 8: ...Introduction ESIE 0303 vi 3 1 4 5 ...
Page 10: ...ESIE 0303 1 2 Part 1 System Outline 3 1 1 5 ...
Page 50: ...Piping Layout ESIE 0303 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 60: ...Wiring Layout ESIE 0303 1 52 Part 1 System Outline 3 1 1 4 5 ...
Page 61: ...ESIE 0302 Wiring Layout Part 1 System Outline 1 53 3 6 Wiring Diagram Wiring diagram ...
Page 62: ...Wiring Layout ESIE 0302 1 54 Part 1 System Outline ...
Page 64: ...ESIE 0303 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 84: ...ESIE 0303 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 87: ...ESIE 0303 Inputs and Outputs Overview Part 3 Troubleshooting 3 5 3 3 4 5 1 ...
Page 88: ...Inputs and Outputs Overview ESIE 0303 3 6 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 94: ...Malfunction Indications and Safeties Overview ESIE 0303 3 12 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 100: ...Checking the Inputs and Outputs ESIE 0303 3 18 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 112: ...Troubleshooting ESIE 0303 3 30 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 114: ...ESIE 0303 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 130: ...ESIE 0303 5 2 Part 5 Maintenance 3 1 5 ...
Page 139: ...ESIE 0303 Index 3 3 4 5 1 Wiring Diagram k 1 53 ...
Page 140: ...ESIE 0303 4 Index 3 1 4 5 ...