ESIE11-02
The Digital Controller
Part 2 – Functional Description
2–35
3
2
4
5
1
Consulting actual
operational
information
The actual operational information that can be consulted in the list of direct parameters consists of:
■
b01
:
Evaporator inlet water temperature,
■
b02
:
Evaporator outlet water temperature,
■
b03
:
Not used,
■
c10
:
Total running hours of the compressor 1,
■
c11
:
Total running hours of the compressor 2,
■
c15
:
Total running hours of the pump.
REMARKS:
■
The parameters
b01
,
b02
and
b03
can also be consulted by the "sensor readout menu". Refer
to "How to consult and modify the ‘sensor readout menu’ parameters" on page 2–34.
■
To reset the timers of parameters
c10
,
c11
and
c15
refer to "Resetting warnings" on page 3–10.
These are direct parameters, refer to "How to consult and modify the direct parameters" on page 2–33.
Summary of Contents for EUWAB10KBZW1
Page 2: ......
Page 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Page 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Page 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Page 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Page 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Page 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Page 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Page 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Page 210: ...ESIE11 02 4 Index 3 1 4 5...