Defrost starting
timers
The table below describes the timers important to start the defrost cycle.
Timer
Description
Steps and conditions
Start-
value
TimConditional 1/2
The minimum time that the defrost start
condition 1 or 2A must be met to start
the defrost cycle.
■
Start of timer
Coil & Ambient below start condition 1 or 2A
AND
Compressor on by thermostat (DI3/4
M1/2Cdetect = closed)
■
Reset of timer (no requests)
Coil & Ambient above start condition 1 or 2
with differential of +2°C on coil temperature
OR
Compressor switched off by thermostat
(DI3/4 M1/2Cdetect = open)
■
End of timer (goes to 0)
Then defrost requests start
150 s
TimOperate1/2
The minimum time that the defrost
condition 2B must be met to start the
defrost cycle. This timer is accumulated
time.
■
Start or continue timer
Coil & Ambient below start condition 2B
AND
Compressor on by thermostat (DI3/4
M1/2Cdetect = closed)
■
Stop of timer
Coil & Ambient above start condition 2B
OR
Compressor switched off by thermostat
(DI3/4 M1/2Cdetect = open)
■
Reset of timer (no requests)
Switch off unit (DI6PumpDetect = open)
2 h
TimComprMin1/2
The minimum time that the compressor
must be switched on before the circuit
can start the defrost cycle.
■
Start of timer
Compressor switched on by thermostat
(DI3/4 M1/2Cdetect = closed)
■
Reset of timer (no requests)
Compressor switch off by thermostat (DI3/4
M1/2Cdetect = open)
20 s
End of TimOperate1/2 AND TimComprMin timer (goes to 0): Then defrost request
Summary of Contents for EUWAB10KBZW1
Page 2: ......
Page 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Page 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Page 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Page 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Page 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Page 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Page 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Page 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Page 210: ...ESIE11 02 4 Index 3 1 4 5...