ESIE11-02
General Outline
1–33
3
1
4
5
1.12
Electrical Specifications: EUWA*10-12KBZW1
Electrical
specifications
The table below contains the electrical specifications
(1)
.
Model
EUWAN10KBZW1 EUWAP10KBZW1 EUWAB10KBZW1 EUWAN12KBZW1 EUWAP12KBZW1 EUWAB12KBZW1
Power supply
Phase
3N~
Frequency
50 Hz
Voltage
400 V
Voltage tolerance
± 10 %
Unit
Starting current
113 A
114 A
139 A
140 A
Nominal running
current
15.9 A
17.2 A
20.5 A
21.8 A
Max. running
current
19.9 A
21.2 A
26.9 A
28.2 A
Recommended
fuses
3 x 25 gL/gG
3 x 32 gL/gG
3 x 32 gL/gG
3 x 40 gL/gG
Fans
Phase
1~
Voltage
230 V
Max. running
current
2.9 A
2.9 A
Compressor
Phase
3~
Voltage
400 V
Starting current
110.0 A
136.0 A
Nom. running
current
13.0 A
17.6 A
Max. running
current
17.0 A
24.0 A
Starting method
Direct on line
Direct on line
Control circuit
Phase
1~
Voltage
230 V
Recommended
fuses
Factory installed
Pump
Phase
__
3~
__
3~
Voltage
__
400.0 V
__
400.0 V
Max. running
current
__
1.3 A
__
1.3 A
Summary of Contents for EUWAB10KBZW1
Page 2: ......
Page 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Page 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Page 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Page 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Page 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Page 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Page 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Page 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Page 210: ...ESIE11 02 4 Index 3 1 4 5...