![Daikin EUWAB10KBZW1 Service Manual Download Page 108](http://html1.mh-extra.com/html/daikin/euwab10kbzw1/euwab10kbzw1_service-manual_501633108.webp)
Functional Description
ESIE11-02
2–22
Part 2 – Functional Description
3
1
2
4
5
Defrost cycle timers
The table below describes the timers that are important in the defrost cycle.
Timer
Description
Startvalue
TimdefrMin
The minimum time that a defrost cycle must be active.
(The timer only starts to count when the compressor is on.)
10 s
TimDefrMax
The maximum time that a defrost can be active.
(The timer only starts to count when the compressor is on.)
10 min
TimMaskC1
The minimum accumulated time interval of compressor ON between stop of a
defrost cycle of circuit 1 and the start of the next defrost cycle of circuit 1.
■
Reset of timer: After power ON or Defrost C1 finished or Mode
≠
Heating
(=> Remark: During the defrost cycle Mode
≠
Heating is ignored, because the
Mode
≠
Heating cannot be detected by the I/O PCB)
(=> Remark: no reset if unit is switched off)
■
Continue of timer: Compressor on by thermostat (DI3M1Cdetect=closed)
■
Stop of timer: Compressor switch off by thermostat (DI3M1Cdetect=open)
■
End of timer (goes to 0): Now defrost is possible
20 min
accumulated
TimMaskC2
The minimum accumulated time interval of compressor ON between stop of a
defrost cycle of circuit 2 and the start of the next defrost cycle of circuit 2.
■
Reset of timer: After power ON or Defrost C2 finished or Mode
≠
Heating
(=> Remark: During the defrost cycle Mode
≠
Heating is ignored, because the
Mode
≠
Heating cannot be detected by the I/O PCB)
(=> Remark: no reset if unit is switched off)
■
Continue of timer: Compressor on by thermostat (DI4M2Cdetect=closed)
■
Stop of timer: Compressor switch off by thermostat (DI4M2Cdetect=open)
■
End of timer (goes to 0): Now defrost is possible
20 min
accumulated
TimComprStop
The time interval that is used if the compressors stops, at the start and stop of the
defrost function.
20 s
TimComprStart
The minimum time interval that is used between the start-up of compressor 1 and
compressor 2.
5 s
Summary of Contents for EUWAB10KBZW1
Page 2: ......
Page 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Page 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Page 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Page 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Page 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Page 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Page 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Page 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Page 210: ...ESIE11 02 4 Index 3 1 4 5...