ESIE11-02
Wiring Layout
1–73
3
1
4
5
X51A
X2 (C3/4, No3, No4)
To A1P MicroChiller compact 2 SE (pump + reverse
valve)
X52A
K1M
NO contact of K1M
X53A
K2M
NO contact of K2M
X55A
(G, GO)
Power supply to MicroChiller compact 2 SE
X56A
(N, L3)
Power supply for evaporator heater tape
X60A
R3T
Evaporator inlet water temperature sensor
X61A
R4T
Evaporator outlet water temperature sensor
X62A
R5T
Cond. inlet water temperature sensor
X63A
S4LP
Low pressure switch circuit 1
X64A
S5LP
Low pressure switch circuit 2
X65A
S10L
Flow contact
X66A
X66A
No use (shortcut)
X70A
X2 (C5, No5)
To A1P (C5, No5)
X71A
X1 (B1, 2, 3, Gnd,
ID1, ID2, ID3, ID4,
ID5, Gnd)
To A1P X1 (B1, B2, B3, Gnd) (ID1, ID2, ID3, ID4, ID5,
Gnd)
X73A
X73A
SER.
Serial communication
X78A
E3H
Evaporator heater tape
X79A
E4H
Evaporator heater tape
X80A
E6H
Buffer heater
X81A
E1H
Crankcase heater 1
X82A
E2H
Crankcase heater 2
X1M
(H3P, H4P, H5P, H6P,
Y3R)
Connection for field wiring
X2M
(L, N, E5H)
Field connection for option OP10 Evap. heater tape
X3M
(G, Go (Option))
S9S
S7S
DO NOT CONNECT
VOLTAGE
Field connection for option kit, EKAC10C (A3P)
and field wiring
X5
Y1R
Reverse valve circuit 1
X6
Y1R
Reverse valve circuit 1
X7
Y2R
Reverse valve circuit 2
X8
Y2R
Reverse valve circuit 2
X9
X9
To fan contactor circuit 1
X10
X10
To fan contactor circuit 2
Connector
Wiring diagram
symbol
Description
Summary of Contents for EUWAB10KBZW1
Page 2: ......
Page 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Page 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Page 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Page 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Page 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Page 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Page 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Page 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Page 210: ...ESIE11 02 4 Index 3 1 4 5...