ESIE11-02
Functional Description
Part 2 – Functional Description
2–23
3
2
4
5
1
Illustration
compressor stop
function
The illustrations below show the defrost cycle without and with compressor stop during the defrost
cycle.
Defrost cycles and
compressor stop
function
The table below describes the minimum and maximum defrost cycles without and with compressor
stop.
Defrost cycle
Start TimDefrMin
Start TimDefrMax
Start TimDefrMask
Time
Yes
No
ON
OFF
ON
OFF
Defrost
BusyC1
Compr.
DORev
Valve
Defrost cycle
Start TimDefrMin
Start TimDefrMax
Start TimDefrMask
Time
Yes
No
ON
OFF
ON
OFF
Defrost
BusyC1
Compr.
DORev
Valve
TimComprStop
Without compressor
stop
Minimum cycle
10 s
TimdefrMin
Maximum cycle
10 min
TimDefrMax
With compressor stop
Minimum cycle
130 s
TimCompr
TimdefrMin
Maximum cycle
12 min
TimCompr
TimDefrMax
Summary of Contents for EUWAB10KBZW1
Page 2: ......
Page 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Page 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Page 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Page 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Page 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Page 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Page 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Page 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Page 210: ...ESIE11 02 4 Index 3 1 4 5...