ESIE11-02
The Digital Controller
Part 2 – Functional Description
2–33
3
2
4
5
1
REMARKS:
a) D=digital, A=analog, I=integer.
b) –2.0 and –7.0 only applicable for units with glycol applications.
c) Used in case dual setpoint is enabled in
p09
or
p34
and dual setpoint digital input is closed.
How to consult and
modify the direct
parameters
For an overview of the menu structure, refer to "Menu Overview" on page 2–38.
1
Press
B
for 5 seconds in the main display.
The -
/
- parameter group is displayed.
2
Press the
C
or
D
key to select the required parameter group.
3
Press the
B
key to enter the selected parameter group.
4
Press the
C
or
D
key to select the required parameter.
5
Press the
B
key to consult the selected parameter.
6
Press the
C
or
D
key to raise, respectively lower the setting of the selected parameter. (Only
valid for read/write parameters.)
7
Press the
B
key to confirm the modified setting.
OR
Press the
A
key to cancel the modified setting.
8
Press the
A
key to return to the parameter group.
9
Press 2 times the
A
key to return to the main display.
If during the procedure no buttons are pressed for 30 seconds, the displayed parameter code or value
will start flashing. After another 30 seconds without pressing any buttons, the controller automatically
returns to the main display without saving any modified parameter.
-
p
-
p09
Changeable digital input selection
S7S
0
=no function
9
=remote cool/heat (only active in
combination with
h06
)
13
=remote dual setpoint
DO NOT SELECT OTHER VALUES
9
0
27
R/W
U
277
I
p34
Changeable digital input selection
S9S
0
=no function
13
=remote dual setpoint
23
=remote on/off (only active in com-
bination with
h07
)
DO NOT SELECT OTHER VALUES
23
0
27
R/W
U
329
I
-
r
-
r01
Cooling setpoint
12.0
7.0
b
25.0
0.1°C
R/W
D
41
A
r02
Cooling difference
3.0
0.3
19.9
0.1°C
R/W
D
42
A
r03
Heating setpoint
30.0
25.0
45.0
0.1°C
R/W
D
43
A
r04
Heating difference
3.0
0.3
19.9
0.1°C
R/W
D
44
A
r21
Cooling setpoint 2
c
12.0
7.0
b
25.0
00.1°C
R/W
D
55
A
r22
Heating setpoint 2
c
30.0
25.0
45.0
0.1°C
R/W
D
56
A
-
t
-
No user or direct parameters accessible
f
-
r
h99
Software release version
R
D
208
I
Parameter
group
Parameter
code
Description
Default
value
Min
Max
Units
Read/
Write
User/
Direct
Modbus
Address
Parameter
type
a
Summary of Contents for EUWAB10KBZW1
Page 2: ......
Page 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Page 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Page 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Page 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Page 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Page 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Page 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Page 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Page 210: ...ESIE11 02 4 Index 3 1 4 5...