The Digital Controller
ESIE11-02
2–34
Part 2 – Functional Description
3
1
2
4
5
How to consult and
modify the user
parameters
REMARK: When user parameters are consulted, the direct parameters are displayed as well.
For an overview of the menu structure, refer to "Menu Overview" on page 2–38.
1
In case of digital controller, press the
A
and
B
keys for approximately 5 seconds until
O
is displayed.
In case of remote user interface, push
S
once.
2
Enter the correct password by using the
C
and
D
keys. The password’s value is
22
.
3
Press the
B
key to confirm the password and to enter the menu,
s
-
p
is displayed.
4
Press the
B
key to consult the parameter settings (=
s
-
p
). (
l
-
p
means consulting the parameter
level, but this function is not used).
The -
/
- parameter group is displayed.
5
Press the
C
or
D
key to select the required parameter group.
6
Press the
B
key to enter the selected parameter group.
7
Press the
C
or
D
key to select the required parameter.
8
Press the
B
key to consult the selected parameter.
9
Press the
C
or
D
key to increase, respectively decrease the setting. (Only valid for read/write
parameters.)
10
Press the
B
key to confirm the modified setting.
OR
Press the
A
key to cancel the modified setting.
11
Press the
A
key to return to the parameter group.
12
Press 2 times the
A
key to return to the main display.
If during the procedure no buttons are pressed for 30 seconds, the displayed parameter code or value
will start flashing. After another 30 seconds without pressing any buttons, the controller automatically
returns to the main display without saving any modified parameter.
How to consult and
modify the ‘sensor
readout menu’
parameters
For an overview of the menu structure, refer to "Menu Overview" on page 2–38.
The
b01
/
b02
/
b03
parameters are part of the "sensor readout menu".
1
Press the
C
or
D
key in the main display.
The
b01
parameter is displayed.
In case no buttons are pressed, the value of the
b01
sensor will be displayed until
C
or
D
is pressed again to select another parameter (
b02
or
b03
).
2
Press the
A
key to return to the main display.
If during the procedure no buttons are pressed for 30 seconds, the displayed parameter code or value
will start flashing. After another 30 seconds without pressing any buttons, the controller automatically
returns to the main display.
Adjusting the
cooling
temperature
setpoint
■
Modify the
r1
cooling setpoint parameter.
This is a direct parameter, refer to "How to consult and modify the direct parameters" on page 2–33.
REMARK: When dual setpoint is enabled (refer to "Selecting dual setpoint control" on page 2–24).
Adjusting the
heating
temperature
setpoint
■
Modify the
r3
heating setpoint parameter.
This is a direct parameter, refer to "How to consult and modify the direct parameters" on page 2–33.
REMARK: When dual setpoint is enabled (refer to "Selecting dual setpoint control" on page 2–24).
Summary of Contents for EUWAB10KBZW1
Page 2: ......
Page 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Page 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Page 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Page 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Page 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Page 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Page 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Page 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Page 210: ...ESIE11 02 4 Index 3 1 4 5...