Functional Description
ESIE11-02
2–24
Part 2 – Functional Description
3
1
2
4
5
1.15
Changeable Digital Inputs
Selecting local or
remote cool/heat
control
User parameter
h0b
in combination with the remote cool/heat selection switch (installed by the
customer) allows the user to select cooling or heating mode without using the
D
or
C
key on
the controller.
■
When user parameter
h0b
is set to
0
(=not active), cooling or heating mode is determined by means
of the controller.
■
When user parameter
h0b
is set to
1
(=active), cooling or heating mode is determined by means of
the remote switch.
REMARK:
■
This is only in case
p09
(changeable digital input selection S7S) has value 9 (default value).
■
In case dual set point function is selected for this function (
p09
=13), the remote cool/heat control
is not activated, meaning the
D
or
C
keys on the controller are still active.
Selecting local or
remote on/off
control
User parameter
h07
in combination with the remote on/off switch (installed by the customer) allows the
user to switch the unit on without using the
D
or
C
key on the controller.
■
When user parameter
h07
is set to
0
(=not active), the unit can only be switched on by means of
the
D
and
C
key on the controller.
■
When user parameter
h07
is set to
1
(=active), the unit can be switched on or off as follows:
■
When the remote on/off switch is opened, the unit is switched off and it is not possible to switch
the unit on/off by pressing the
D
or
C
key on the controller (5 sec.)
■
When the remote on/off switch is closed, the unit is switched on and it is possible to switch the
unit on/off by pressing the
D
or
C
key on the controller (5 sec.)
REMARK:
■
This is only in case
p34
(changeable digital input selection S9S) has value 23 (default value).
■
In case dual set point function is selected for this function (
p34
=13), the remote on/off control is not
activated.
Selecting dual
setpoint control
User parameters
p09
(changeable digital input selection S7S) and
p34
(changeable digital input
selection S9S) can be used to assign the dual setpoint control to S7S or S9S.
There are 3 different controls available for 2 different changeable digital inputs (S7S and S9S):
■
p09
: changeable digital input selection S7S
■
0=no function
■
9=remote cool/heat
■
13=remote dual setpoint
■
p34
: changeable digital input selection S9S
■
0=no function
■
13=remote dual setpoint
■
23=remote on/off
When the dual setpoint switch is open, the first setpoint is activated (
r01
cooling setpoint or
r03
heating
setpoint, depending on cooling or heating operation).
When the dual setpoint switch is closed, the second setpoint is activated (
r21
cooling setpoint 2 or
r22
heating setpoint 2, depending on cooling or heating operation).
Summary of Contents for EUWAB10KBZW1
Page 2: ......
Page 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Page 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Page 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Page 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Page 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Page 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Page 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Page 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Page 210: ...ESIE11 02 4 Index 3 1 4 5...