Operating instructions
52
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
6
x
Parameter settings
6.12 Parameter level "Basic Configuration"
This parameter level appears only if:
– during initial commissioning, during the question "Use Stand-
ard Config?" the answer "No" has been selected or
– after, in the rotary switch position
"Configuration"
, level
"Setup"
the parameter [System Config] has been set to "inac-
tive" or "delete".
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Boiler Function
Setting of system functionality of the device in the RoCon system (factory setting not pre-
sent).
The standard value of this parameter is "Single" and thus applies to a Daikin
Altherma EHS(X/H) in self-contained operating mode.
With value settings "Slave 1" to "Slave 8" the Daikin Altherma EHS(X/H) works as a heater
module and waits for the demand for an optional cascade regulator.
These settings are not currently usable.
N
E
Single,
Slave 1
...
Slave 8
Single
-
Unmixed Circ Config Setting the heating circuit ID for the direct heating circuit of the Daikin Altherma EHS(X/H).
The heating circuit ID must be unique in the entire RoCon system. There should be no over-
lap with the heating circuit IDs of optional mixer circuits (parameter [HC Assignment],
N
E
0 - 15
0
1
BUS ID HS
Settings can only be changed if more than 1 heat generator is incorporated in the RoCon sys-
tem. Several heat generators incorporated in the heating installation must be regarded as a
special application. If necessary contact Daikin service technician.
N
E
0 - 7
0
1
Time Master
Activation of a system-wide time master RoCon. The time master synchronises all controllers
in the Can system with the date and time set at the time master. The input of time and date
can no longer be set at any other control unit in the system. There may be only one time mas-
ter in the entire system. The parameter is not available if the time master parameter is acti-
vated at a different controller in the RoCon system.
N
E
Off
On
On
-
System Config
The system configuration of the unit, consisting of the sensor configuration and data bus con-
figuration, can be deleted, activated and deactivated with this parameter. If you answer "Yes"
to the enquiry about using the standard configuration, when starting the unit for the first time,
the settings required for the basic equipment of the heat generator are activated automatical-
ly (see section 6.2.1, tab. 6-1).
N
E
Inactive,
Active,
Delete
Inactive
-
Tab. 6-14 Parameter in the level "Basic Configuration"
6.13
Parameter levels for the EHS157068 mixer module
The parameter levels, parameter priorities, setting ranges and
associated functions are essentially the same as those described
in the preceding sections.
In some cases there exist at individual levels a restricted scope
of available parameters.
The description below relates only to the sections indicated.
Areas where there are significant differences are described in
greater detail.
Rotary switch setting: Info
see section 6.10
When setting the control unit to "Mix Valve #X" (terminal
function), the displayed values refer to the components con-
nected (pump, mixer valve,...) connected to the EHS157068 of
the mixer circuit allocated using the device ID.
When setting a room station EHS157034 to "Living Room", that
has been allocated to the mixer module via the heating circuit ID,
the parameter [T-Room adj] is available. The rotary switch can be
used to change the room target temperature to the range -5 K to
+5 K. This function is not available if the EHS157034 is used as
a remote control in terminal function.
Rotary switch setting: Operating Mode
see section 6.4
Rotary switch setting: Set Temp Day
see section 6.5
Rotary switch setting: Set Temp Night
see section 6.6
Rotary switch setting: DHW Set Temp
No function
Rotary switch setting: DHW Install
No function
Rotary switch setting: Time Program
see section 6.8
Rotary switch setting: Configuration
(see section 6.13.1 and 6.13.2.
Rotary switch setting: Remote Param
see section 6.9
Parameter Reset
Resets all customer-specific parameter settings to factory setting.
N
E
Off
On
Off
-
Timeprog Reset
Resets all permanent time programmes to factory setting (see tab. 3-9).
E
E
Off
On
Off
-
Return
This parameter is used only to exit the special level.
E
E
Tab. 6-13 Parameter in the level "Sonderfunktion"
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF