Operating instructions
32
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
4
x
Initial start-up
4
Initial start-up
In addition to the commissioning instructions listed in
this chapter, the specific commissioning instructions
listed in the installation instructions for the Daikin
Altherma EHS(X/H) must be complied with.
The RoCon system offers a very wide range of application and
extension possibilities.
The individual RoCon system components communicate via the
CAN data bus. For this reason, the circuit boards RoCon BM1
and the control units RoCon B1 of the Daikin
Altherma EHS(X/H), and possibly the optional system compo-
nents room station
EHS157034
and mixer module
EHS157068
are connected together via data bus lines.
These system components must be allocated unique functional
IDs, so that the data exchange and the allocation functions
without any problems within the RoCon system.
In many applications, nothing needs to be changed on the basic
settings. The more RoCon system components that are inte-
grated in the RoCon system, the more adjustments that need to
be made during the initial commissioning or when extending the
heating system.
The allocation of the functional IDs is easiest carried out via the
installation menu "Setup Wizard". Most IDs can also be adapted
subsequently to the conditions by means of individual parameter
settings in the specific parameter levels (see chapter 6).
a) If
no optional RoCon system components are connected
to the Daikin Altherma EHS(X/H)
, in the RoCon system, just
the circuit board RoCon BM1 and the integrated control unit
RoCon B1 communicate with each other.
Adaption of the IDs is not necessary.
The question displayed during initial commissioning "Use
standard configuration?" can be confirmed by "Yes".
b) If
optional RoCon system components
such as
EHS157034
and / or
EHS157068
are connected, adaption to
the IDs may be necessary.
4.1
Fundamental aspects of the IDs and authorisations in the RoCon system
In the RoCon system, the following functional IDs exist, which are
relevant for data exchange of the RoCon system components:
ID / function
System components
Parameter
Comments
Heating circuit IDs
Unique numbering of a heating circuit
in the heating system in the RoCon
system. A maximum of 16 heating cir-
cuits can be controlled.
Daikin Altherma EHS(X/H)
(RoCon BM1)
[Unmixed Circ Config]
Factory setting = 0
Should not normally be changed.
1)
Room station EHS157034
[HC Assignment]
See tab. 6-1
Factory setting = Off
Adaption necessary because there are dif-
ferent heating circuits in the system and /
or the parameter [Master-RoCon] = On
Mixer module EHS157068
[HC Assignment]
Factory setting = Off
Must always be adapted to the setting of
the address switch (fig. 4-2).
Heat generator ID
Unique numbering of a heat gen-
erator in the RoCon system.
1)
Daikin Altherma EHS(X/H)
(RoCon BM1)
[BUS ID HS]
Factory setting = 0
Should not normally be changed.
1)
Mixer module EHS157068 [Boiler Assignment]
Factory setting = 0
Should not normally be changed.
1)
Defines the heat generator that supplies
the allocated heating circuit with heat.
Terminal ID
Unique numbering of a control unit
RoCon B1 or EHS157034, from
which a heat generator and / or a
mixer module in the RoCon system
can be controlled remotely.
The authorisation for remote control
can be allocated to up to 10 control
units in the RoCon system. If remote
control in the RoCon system is to be
possible, then the control unit must
be allocated the ID "0".
Daikin Altherma EHS(X/H)
(RoCon BM1)
[Terminaladress]
See tab. 6-1
Factory setting = Off
The value should be set to "0" if at least 1
mixer module is connected in the RoCon
system, and the mixer circuit is to be op-
erated from the heat generator.
Room station EHS157034
[Terminaladress]
see tab. 6-1 or
tab. 6-15 - depending
on the set heating cir-
cuit ID and the current
operating mode
Factory setting = Off
The value must be set to a unique nu-
merical value in the RoCon system, if the
room station system components are to be
remotely controlled using a valid device ID.