Parameter settings
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
41
6
Parameter settings
6.1
Explanation of the parameter tables
The parameter tables listed in the sections 6.2 to 6.11 contain im-
portant information concerning all parameters that are available
in the individual rotary switch setting on the controller (1st. menu
level, 2nd. menu level).
In addition to the parameter designations, the tables contain de-
tails for the setting ranges, factory settings, setting options or
setting step distances and brief function explanations.
In addition, they provide explanation of the access rights for the
operation of the controller. The following abbreviations are
available for appropriate characterisation:
BE
Access right for the operator
HF
Access permission with Technician password
If different settings appear in the BF and HF columns, the
user must log in as a technician so as to be able to
access the parameter level to change the status set in
the HF column (see chapter 3.6.1).
Status:
N
Not visible
E
Visible and configurable
S
Visible
6.2
Rotary switch setting: Configuration
6.2.1 Level "Setup"
Sub
-
lev
e
l
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
LCD Brightness
Display brightness
E
E
0 - 100 %
50%
10 %
LCD Illum Time
Duration of display lighting
E
E
5 - 120 s
30 s
1 s
Language
Language of the display text in the operating panel
E
E
Deutsch
English
French
Dutch
Italian
Spanish
Portuguese
Deutsch
-
Date
Current date in format day / month / year. The current day of the week is calculated
automatically from the date.
E
E
Time
Time in format hours / minutes.
E
E
Keylock Function
Release of the keylock function:
Off: Button block cannot be activated.
On: The button block can be activated using the rotary switch (see chapter 3.3).
E
E
Off
On
Off
-
Access Rights
Entering access code. Setting character by character like a combination lock
(see chapter 3.6.1).
E
E
0 - 9
0000
1
RoCon U1 assign
Display only on connected
room station:
Function of the room station EHS157034 in the CAN-data bus system:
Living Room: Control panel for the heating circuit assigned in the parameter [HC As-
signment].
Mixing Valve: Mixer circuit operating unit (as a mixer circuit extension or as a free-
standing mixer circuit controller)
In addition to the aforementioned functions, the room station can be basically used as
a remotely controlled unit of the Daikin Altherma EHS(X/H) and the entire RoCon sys-
tem (with activated terminal function) (see chapter 4.1 and 4.4.2).
N
E
Living Room,
Mixing Valve
Living Room
-
Master-RoCon
Display only on connected
room station:
Setting the Master-RoCon function
Off: Deactivated
On: Function active
On a room station EHS157034, whose heating circuit ID is set to a direct heating cir-
cuit, the Master-RoCon function can be activated (see chapter 4.4.4). Several room
stations with active Master-RoCon function in the system are possible, however only
one room station is possible that is allocated to the same heat generator.
All settings on the room station EHS157034 act, with activated Master-RoCon function,
like settings on the control unit RoCon B1 B1 of the allocated heat generator. As a re-
sult, the functions for hot water preparation can also be remotely operated from the
room station.
N
E
Off
On
Off
-
Outdoor type
Type exterior heat pump unit
0: No Off selection
1: 4 kW
2: 6 kW
3: 8 kW
4: 11 kW
5: 14 kW
6: 16 kW
N
E
0 - 6
0
1